All digital inputs can be programmed to these functions
[0]
No operation No reaction to signals transmitted to
terminal.
[1]
Reset
Resets frequency converter after a trip/alarm.
Not all alarms can be reset.
[2]
Coast inverse Leaves motor in free mode. Logic
0
⇒
coasting stop.
(Default Digital input 27): Coasting stop,
inverted input (NC).
[3]
Coast and
reset inverse
Reset and coasting stop, inverted input (NC).
Leaves motor in free mode and resets the
frequency converter. Logic 0
⇒
coasting stop
and reset.
[5]
DC-brake
inverse
Inverted input for DC braking (NC).
Stops motor by energising it with a DC
current for a certain time period. See
parameter 2-01 DC Brake Current
to
parameter 2-03 DC Brake Cut In Speed [RPM]
.
The function is only active when the value
in
parameter 2-02 DC Braking Time
is
different from 0. Logic 0
⇒
DC braking.
This selection is not possible when
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
.
[6]
Stop inverse
Stop inverted function. Generates a stop
function when the selected terminal goes
from logical level 1 to 0. The stop is
performed according to the selected ramp
time
•
Parameter 3-42 Ramp 1 Ramp Down
Time
•
Parameter 3-52 Ramp 2 Ramp Down
Time
NOTICE
When the frequency converter is at
the torque limit and has received a
stop command, it may not stop by
itself. To ensure that the frequency
converter stops, configure a digital
output to
[27] Torque limit & stop
and
connect this digital output to a digital
input that is configured as coast.
[7]
External
Interlock
Same function as coasting inverse and stop
inverse, but this option generates the alarm
message
External fault
on the display when
the terminal programmed for coast inverse
has signal 0. The alarm message is also
active via digital outputs and relay outputs,
if programmed for external interlock. When
the external interlock is removed, the alarm
can be reset using a digital input or the
[RESET] key. A delay can be programmed in
parameter 22-00 External Interlock Delay
. After
applying a signal to the input, the reaction
described above is delayed with the time set
in
parameter 22-00 External Interlock Delay
.
[8]
Start
Select start for a start/stop command. Logic
1=start, logic 0=stop.
(Default: Digital input 18).
[9]
Latched start The motor starts, if a pulse is applied for
minimum. 2 ms. The motor stops when stop
inverse is activated.
[10] Reversing
Changes direction of motor shaft rotation.
Select Logic 1 to reverse. The reversing
signal only changes the direction of rotation.
It does not activate the start function. Select
both directions in
.
(Default: Digital input 19).
[11] Start
reversing
Used for start/stop and for reversing on the
same wire. Signals on start are not allowed
at the same time.
[14] Jog
Used for activating jog speed. See
.
(Default: Digital input 29)
[15] Preset
reference on
Used for shifting between external reference
and preset reference. It is assumed that
External/preset [1]
has been selected in
parameter 3-04 Reference Function
. Logic
0=external reference active; logic 1=1 of the
8 preset references is active.
[16] Preset ref bit
0
Enables a choice between 1 of the 8 preset
references according to
[17] Preset ref bit
1
Enables a choice between 1 of the 8 preset
references according to
[18] Preset ref bit
2
Enables a choice between 1 of the 8 preset
references according to
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 3.10 Digital Inputs Preset Reference
Bit
[19] Freeze ref
Freezes actual reference. The frozen
reference is now the point of enable/
condition for speed up and speed down to
be used. If speed up/down is used, the
speed change always follows ramp 2
(
parameter 3-51 Ramp 2 Ramp Up Time
and
parameter 3-52 Ramp 2 Ramp Down Time
) in
the range 0 –
3-03 Maximum Reference
. (For
Parameter Descriptions
VLT
®
HVAC Drive FC 102
70
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02
3
3