22-26 Dry Pump Function
Select desired action for dry-pump operation.
Option:
Function:
[0]
*
Off
[1]
Warning
NOTICE
To use dry-pump detection:
1.
Enable
low-power detection
in
parameter 22-21 Low Power
Detection
.
2.
Commission
low-power detection
using either parameter group
22-3* No-flow Power Tuning No
Flow Power Tuning
, or
parameter 22-20 Low Power Auto
Set-up
NOTICE
Do not set
to
[13] Infinite auto reset
, when
parameter 22-26 Dry Pump Function
is set
to
[2] Alarm
. Doing so causes the
frequency converter to continuously cycle
between running and stopping when a
dry-pump condition is detected.
NOTICE
For frequency converters with constant-
speed bypass
If an automatic bypass function starts the
bypass at persistent alarm conditions,
disable the bypass’s automatic bypass
function, if
[2] Alarm
or
[3] Man. Reset
Alarm
is selected as the dry-pump
function.
The frequency converter continues to run, but
activates a dry-pump warning
(Warning 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate a
warning to other equipment.
[2]
Alarm
The frequency converter stops running and
activates a dry-pump alarm
(Alarm 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
[3]
Man.
Reset
Alarm
The frequency converter stops running and
activates a dry-pump alarm
(Alarm 93, Dry
pump)
. A frequency converter digital output or a
serial communication bus can communicate an
alarm to other equipment.
22-26 Dry Pump Function
Select desired action for dry-pump operation.
Option:
Function:
[4]
Stop and
Trip
22-27 Dry Pump Delay
Range:
Function:
10 s
*
[0 - 600
s]
Defines for how long the dry-pump condition
must be active before activating a warning or
an alarm.
The frequency converter waits for the no-flow
delay time (
22-24 No-Flow Delay
) to expire
before the timer for the dry-pump delay starts.
3.20.2 22-3* No-flow Power Tuning
If not selecting
Auto Set Up
in
, the tuning sequence is:
1.
Close the main valve to stop flow.
2.
Run with motor until the system has reached
normal operating temperature.
3.
Press [Hand On] and adjust speed for approxi-
mately 85% of rated speed. Note the exact speed.
4.
Read power consumption either by looking for
actual power in the data line in the LCP or call
4a
or
4b
in Main
Menu.
Note the power readout.
5.
Change speed to approximately 50% of rated
speed. Note the exact speed.
6.
Read power consumption either by looking for
actual power in the data line in the LCP or call
6a
or
6b
in Main
Menu.
Note the power readout.
7.
Programme the speeds used in:
7a
Parameter 22-32 Low Speed [RPM]
.
7b
Parameter 22-33 Low Speed [Hz]
.
7c
Parameter 22-36 High Speed [RPM]
.
7d
Parameter 22-37 High Speed [Hz]
8.
Programme the associated power values in:
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.