3.16 Parameters: 16-** Main Menu - Data
Readouts
3.16.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
*
[0 - 65535 ] View the control word sent from the frequency
converter via the serial communication port in
hex code.
16-01 Reference [Unit]
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999 -
999999
ReferenceFeed-
backUnit]
View the present reference
value applied on impulse or
analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode
(Hz, Nm, or
RPM).
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 - 200
%]
View the total reference. The total reference
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ] View the status word sent from the frequency
converter via the serial communication port in
hex code.
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-100 - 100 %] View the 2-byte word sent with the status
word to the bus master reporting the
main actual value.
16-09 Custom Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[-999999.99 -
999999.99
CustomRea-
doutUnit]
View the user-defined readouts
as defined in
parameter 0-30 Custom Readout
Unit
,
, and
parameter 0-32 Custom Readout
Max Value
.
3.16.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 -
10000
kW]
Displays motor power in kW. The value shown
is calculated based on the actual motor
voltage and motor current. The value is
filtered, and therefore approximately 1.3 s may
pass from when an input value changes to
when the data readout values change. The
resolution of readout value on fieldbus is in
10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
*
[0 -
10000 hp]
View the motor power in hp. The value
shown is calculated based on the actual
motor voltage and motor current. The value is
filtered, and therefore approximately 1.3 ms
may pass from when an input value changes
to when the data readout values change.
16-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 6000 V] View the motor voltage, a calculated value
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6500 Hz] View the motor frequency, without
resonance damping.
16-14 Motor current
Range:
Function:
0 A
*
[0 - 10000
A]
View the motor current measured as a mean
value, I
RMS
. The value is filtered, and thus
approximately 1.3 s may pass from when an
input value changes to when the data
readout values change.
16-15 Frequency [%]
Range:
Function:
0 %
*
[-100 -
100 %]
View a 2-byte word reporting the actual motor
frequency (without resonance dampening) as a
percentage (scale 0000-4000 hex) of
parameter 4-19 Max Output Frequency
. Set
parameter 9-16 PCD Read Configuration
index 1
to send it with the status word instead of the
MAV.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
130
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02