3.4.4 3-5* Ramp 2
Selecting ramp parameters, see parameter group
3-4*
Ramp 1
.
3-51 Ramp 2 Ramp Up Time
Range:
Function:
Size
related
*
[0.05
- 3600
s]
Enter acceleration time from 0 Hz to
if Asynchronous
motor is selected. Enter acceleration time
from 0 RPM to
if
PM motor is selected. Select a ramp-down
time such that the output current does not
exceed the current limit in
during ramping. See ramp-down time
in
3-52 Ramp 2 Ramp Down Time
Range:
Function:
Size
related
*
[0.05
- 3600
s]
Enter deceleration time from
to 0 Hz if Asynchronous motor is
selected. Enter deceleration time from
to 0 RPM if PM
motor is selected. Select a ramp-down time
such that the output current does not
exceed the current limit in
during ramping. See ramp-up time in
3.4.5 3-8* Other Ramps
3-80 Jog Ramp Time
Range:
Function:
Size
related
*
[0.05
- 3600
s]
Enter the jog ramp time, i.e. the
acceleration/deceleration time between 0 Hz
to
. Ensure that the
resultant output current required for the
given jog ramp time does not exceed the
current limit in
. The jog
ramp time starts upon activation of a jog
signal via the control panel, a selected
digital input, or the serial communication
port.
3-81 Quick Stop Ramp Time
Range:
Function:
Size
related
*
[0.05 -
3600 s]
Enter the quick stop ramp time from the
to 0 Hz. During
ramping, no over-voltage may arise in the
inverter, nor may the generated current
exceed the limit in
is
activated by means of a signal on a
selected digital input or via the serial
communication port.
Parameters
VLT
®
HVAC Basic Drive FC 101 Programming Guide
34
MG18B302 - Rev. 2013-09-02
3
3