8 Specifications
8.1 Electrical Data and Wire Sizes
M
Mains Supply 3 x 380 - 480VAC
Frequency Converter
PK37
PK55
PK75
P1K1
P1K5
P2K2
Typical Shaft Output [kW]
0.37
0.55
0.75
1.1
1.5
2.2
Typical Shaft Output [HP] at 460V
0.5
0.75
1.0
1.5
2.0
3.0
Output current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB799.10
Continuous (3 x 380-440V) [A]
1.3
1.8
2.4
3.0
4.1
5.2
Intermittent (3 x 380-440V) [A]
2.1
2.9
3.8
4.8
6.6
8.3
Continuous (3 x 441-480V) [A]
1.2
1.6
2.1
3.0
3.4
4.8
Intermittent (3 x 441-480V) [A]
1.9
2.6
3.4
4.8
5.4
7.7
Continuous kVA (400V AC) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
Continuous kVA (460V AC) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
Max. cable size: (mains, motor, brake)
[mm
2
/ AWG]
6/10
Max. input current
ON
WARNING
ALARM
Bus MS
NS2
NS1
130BB800.10
Continuous (3 x 380-440V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
Intermittent (3 x 380-440V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
Continuous (3 x 441-480V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
Intermittent (3 x 441-480V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
Max. pre-fuses IEC/UL [A]
25
Power loss at max. load [W]
35
42
46
58
62
88
Efficiency
0.93
0.95
0.96
0.96
0.97
0.97
Weight
[kg]
9.8
Specifications
VLT
p
Decentral Drive FCD 302 Operating Instructions
MG.04.F2.02 - VLT
p
is a registered Danfoss trademark
71
8
8
inverter.ru (812) 702-47-50