Alarm word and extended status word
Bit
Hex
Dec
Alarm word
Warning word
Extended status word
0
00000001
1
Brake check
Brake check
Ramping
1
00000002
2
Pwr. card temp
Pwr. card temp
AMA running
2
00000004
4
Ground fault
Ground fault
Start CW/CCW
3
00000008
8
Ctrl. card temp
Ctrl. card temp
Slow down
4
00000010
16
Ctrl. word TO
Ctrl. word TO
Catch up
5
00000020
32
Overcurrent
Overcurrent
Feedback high
6
00000040
64
Torque limit
Torque limit
Feedback low
7
00000080
128
Motor Th over
Motor Th over
Output current high
8
00000100
256
Motor ETR over
Motor ETR over
Output current low
9
00000200
512
Inverter overld.
Inverter overld.
Output freq high
10
00000400
1024
DC under volt
DC under volt
Output freq low
11
00000800
2048
DC over volt
DC over volt
Brake check ok
12
00001000
4096
Short circuit
DC voltage low
Braking max
13
00002000
8192
Inrush fault
DC voltage high
Braking
14
00004000
16384
Mains ph. loss
Mains ph. loss
Out of speed range
15
00008000
32768
AMA not OK
No motor
OVC active
16
00010000
65536
Live zero error
Live zero error
–
17
00020000
131072
Internal fault
10 V low
–
18
00040000
262144
Brake overload
Brake overload
–
19
00080000
524288
U phase loss
Brake resistor
–
20
00100000
1048576
V phase loss
Brake IGBT
–
21
00200000
2097152
W phase loss
Speed limit
–
22
00400000
4194304
Fieldbus fault
Fieldbus fault
–
23
00800000
8388608
24 V supply low
24 V supply low
–
24
01000000
16777216
Mains failure
Mains failure
–
25
02000000
33554432
1.8 V Supply low
Current limit
–
26
04000000
67108864
Brake resistor
Low temp
–
27
08000000
134217728
Brake IGBT
Voltage limit
–
28
10000000
268435456
Option change
Unused
–
29
20000000
536870912
Drive initialized
Unused
–
30
40000000
1073741824
Safe Torque Off
Unused
–
Table 6.4 Description of Alarm Word, Warning Word, and Extended Status Word
The alarm words, warning words, and extended status words can be read via fieldbus or optional fieldbus for diagnosis.
Also, refer to
parameter 16-90 Alarm Word
,
parameter 16-92 Warning Word
, and
parameter 16-94 Ext. Status Word
.
Bit
Hex
Dec
Alarm word 2
Warning word 2
0
00000001
1
–
Start Delayed
1
00000002
2
–
Stop Delayed
9
00000200
512
Discharge Temperature High
Discharge Temperature High
10
00000400
1024
Start Limit
–
11
00000800
2048
Speed Limit
–
Table 6.5 Description of Alarm Word 2 and Warning Word 2
Troubleshooting
Service Guide
MG94A502