Replace the corresponding current sensor if the reading is
greater than 15 mV.
and
list approximate resistance readings
for individual D-sized units based on power and voltage
rating, and the current scaling card.
through
list approximate resistance readings for parallel
drive systems based on power and voltage rating, and the
current scaling card. When measuring with the signal test
board, the reading could be higher due to meter lead
resistance. A reading of no resistance indicates a missing
scaling card.
Scaling resistance
measured in
Ω
Model
FC 102, FC 103, and
FC 202
FC 302
3.8
N55K
N45K
3.1
N75K
N55K
2.6
N90K
N75K
2.6
N110
N90K
5.1
N150
N110
4.2
N160
N150
Table 8.7 Scaling Resistance, D1h–D4h Units, 200–240 V
Scaling resistance
measured in
Ω
Model
FC 102, FC 103, and
FC 202
FC 302
4.6
N110
N90k
3.8
N132
N110
3.1
N160
N132
2.6
N200
N160
5.1
N250
N200
4.2
N315
N250
Table 8.8 Scaling Resistance, D1h–D8h Units, 380–480/500 V
Scaling resistance
measured in Ω
Model
FC 102, FC 103, and
FC 202
FC 302
5.9
N75k
N55k
5.9
N90k
N75k
5.9
N110
N90k
5.9
N132
N110
5.0
N160
N132
4.0
N200
N160
3.2
N250
N200
2.7
N315
N250
5.6
N400
N315
Table 8.9 Scaling Resistance, D1h–D8h Units, 525–690 V
Scaling resistance
measured in Ω
Model
Drive modules
FC 102, FC 103,
and FC 202
FC 302
4.2
N500
N450 2-module system
2.6
N560
N500 4-module system
5.1
N630
N560 4-module system
5.1
N710
N630 4-module system
4.2
N800
N710 4-module system
4.2
N1M0
N800 4-module system
Table 8.10 Scaling Resistance, Parallel Drive Systems,
6-pulse, 380–500 V
Scaling resistance
measured in Ω
Model
Drive modules
FC 102, FC 103,
and FC 202
FC 302
5.6
N630
N560 2-module system
3.2
N710
N630 4-module system
2.7
N800
N710 4-module system
2.7
N900
N800 4-module system
5.6
N1M0
N900 4-module system
5.6
N1M2
N1M0 4-module system
Table 8.11 Scaling Resistance, Parallel Drive Systems,
6-pulse, 525–690 V
Scaling resistance
measured in Ω
Model
Drive modules
FC 102, FC 103,
and FC 202
FC 302
2.6
N315
N250 2-module system
5.1
N355
N315 2-module system
5.1
N400
N355 2-module system
4.2
N450
N400 2-module system
4.2
N500
N450 2-module system
2.5
N560
N500 4-module system
5.1
N630
N560 4-module system
5.1
N710
N630 4-module system
4.2
N800
N710 4-module system
4.2
N1M0
N800 4-module system
Table 8.12 Scaling Resistance, Parallel Drive Systems,
12-pulse, 380–500 V
Test Procedures
Service Guide
MG94A502
Danfoss A/S © 02/2019 All rights reserved.
115
8
8