0-12 This Set-up Linked to
Option:
Function:
OR
2. While still in Set-up 1, using
,
copy Set-up 1 to Set-up 2. Then set
to
[2] Set-up 2
. This will start
the linking process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 3.2
After the link is complete,
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a ‘not changeable during
operation’ parameter, e.g.
, in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between
Set-up 1 and Set-up 2 during operation is now
possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 - 255 ] View a list of all the set-ups linked by means of
. The parameter has one
index for each parameter set-up. The parameter
value displayed for each index represents which
set-ups are linked to that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2 Example: Set-up 1 and Set-up 2 are
linked
0-14 Readout: Prog. Set-ups / Channel
Range:
Function:
0
*
[-2147483648
- 2147483647 ]
View the setting of
for each of the four different
0-14 Readout: Prog. Set-ups / Channel
Range:
Function:
communication channels. When the
number is displayed in hex, as it is in the
LCP, each number represents one channel.
Numbers 1-4 represent a set-up number; ‘F’
means factory setting; and ‘A’ means active
set-up. The channels are, from right to left:
LCP, FC-bus, USB, HPFB1.5.
Example: The number AAAAAA21h means
that the FC-bus selected Set-up 2 in
, the LCP selected
Set-up 1 and all others used the active set-
up.
3.2.2 0-2* LCP Display
Define the variables displayed in the Graphical Local
Control Panel.
NOTE
Please refer to
and
for information on how to write display
texts.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable for display in line
1, left position. Default setting is
application dependent.
[37]
Display Text 1
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communi-
cation.
[38]
Display Text 2
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communi-
cation.
[39]
Display Text 3
Enables an individual text string to
be written, for display in the LCP or
to be read via serial communi-
cation.
[89]
Date and Time
Readout
Displays the current date and time.
[953]
Profibus Warning
Word
Displays Profibus communication
warnings.
[1005] Readout Transmit
Error Counter
View the number of CAN control
transmission errors since the last
power-up.
[1006] Readout Receive
Error Counter
View the number of CAN control
receipt errors since the last power-
up.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
28
MG16H102 - VLT
®
is a registered Danfoss trademark
3
3