23-54 Reset Energy Log
Option:
Function:
Select
[1] Do reset
to reset all values in the
Energy Log counters shown in
. After pressing OK the setting of the
parameter value will automatically change to
[0] Do not reset
.
[0] Do not reset
[1] Do reset
3.18.6 23-6* Trending
Trending is used to monitor a process variable over a
period of time and record how often the data falls into
each of ten user-defined data ranges. This is a convenient
tool to get a quick overview indicating where to focus on
improvement of operation.
Two sets of data for Trending can be created to make it
possible to com current values for a selected operating
variable with data for a certain reference period, for the
same variable. This reference period can be pre-
programmed (
and
). The two sets of data can be read from
(current) and
(reference).
It is possible to create Trending for following operation
variables:
-
Power
-
Current
-
Output frequency
-
Motor Speed
The Trending function includes ten counters (forming a
bin) for each set of data containing the numbers of
registrations reflecting how often the operating variable is
within each of ten pre-defined intervals. The sorting is
based on a relative value of the variable.
The relative value for the operating variable is
Actual/Rated * 100%
for Power and Current and
Actual/Max * 100%
for Output Frequency and Motor Speed.
The size of each interval can be adjusted individually, but
will default be 10% for each. Power and Current can
exceed rated value, but those registrations will be included
in 90%-100% (MAX) counter.
Relative value
operating variable
Counter 1: +1
Counter 0: +5
Counter 2: +0
Counter 3: +1
Counter 4: +0
Counter 5: +11
Counter 6: +1
Counter 7: +2
Counter 8: +6
Counter 9: +0
130BA281.10
80
70
50
60
30
40
10
20
%
90
100
Illustration 3.60
Once a second, the value of the operating variable
selected is registered. If a value has been registered to
equal 13%, the counter “10% - <20%” will be updated with
the value “1”. If the value stays at 13% for 10s, then “10”
will be added to the counter value.
The contents of counters can be displayed as bars on LCP.
Select
Quick Menu
⇒
Loggings
:
Trending Continued Bin/
Trending Timed Bin/Trending Comson
.
NOTE
The counters starts counting whenever the frequency
converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEPROM data are updated once per
hour.
23-60 Trend Variable
Option:
Function:
Select the desired operating variable to be
monitored for Trending.
[0]
*
Power [kW]
Power yielded to the motor. Reference for
the relative value is the rated motor power
programmed in
or
. Actual value can be
read in
or
.
[1]
Current [A]
Output current to the motor. Reference for
the relative value is the rated motor current
programmed in
. Actual
value can be read in
[2]
Frequency
[Hz]
Output frequency to the motor. Reference
for the relative value is the maximum output
frequency programmed in
. Actual value can be read in
[3]
Motor Speed
[RPM]
Speed of the motor. Reference for relative
value is the maximum motor speed
programmed in
Parameter Description