2-10 Brake Function
Option:
Function:
Available selections depend on par. 1-10
Motor Construction
:
[0] Asynchron:
[0] off
[1] Resistor brake
[2] AS brake
[1] PM non salient:
[0] off
[1] Resistor brake
[0] *
Off
No brake resistor installed.
[1]
Resistor brake
Brake resistor incorporated in the system, for dissipation of surplus brake energy as heat. Con-
necting a brake resistor allows a higher DC link voltage during braking (generating operation).
The Resistor brake function is only active in frequency converters with an integral dynamic brake.
[2]
AC brake
AC Brake will only work in Compressor Torque mode in par. 1-03
2-17 Over-voltage Control
Option:
Function:
[0]
Disabled
No OVC required.
[2] *
Enabled
Activates OVC.
will not have effect
when par. 1-10
Motor Construction
= [1] PM, non sa-
lient SPM.
The ramp time is automatically adjusted to avoid
tripping of the frequency converter.
3-02 Minimum Reference
Range:
Function:
Size rela-
ted*
[ -999999.999 - par. 3-03 Refer-
enceFeedbackUnit]
Enter the Minimum Reference. The Minimum Reference is the lowest value obtainable by sum-
ming all references. The Minimum Reference value and unit matches the configuration choice
made in par. 1-00
and par. 20-12
Reference/Feedback Unit
, respectively.
This parameter is used in open loop only.
3-04 Reference Function
Option:
Function:
[0] *
Sum
Sums both external and preset reference sources.
[1]
External/Preset
Use either the preset or the external reference source.
Shift between external and preset via a command on a digital input.
3-10 Preset Reference
Array [8]
Range:
Function:
0.00 %*
[-100.00 - 100.00 %]
Enter up to eight different preset references (0-7) in this parameter, using array programming.
The preset reference is stated as a percentage of the value Ref
MAX
(par. 3-03
Maximum Refer-
ence
, for closed loop see par. 20-14
Maximum Reference/Feedb.
). When using preset references,
select Preset ref. bit 0 / 1 / 2 [16], [17] or [18] for the corresponding digital inputs in parameter
group 5-1* Digital Inputs.