Q3-4 Application Settings
Q3-40 Fan Functions
Q3-41 Pump Functions
Q3-42 Compressor Functions
Par. 22-20
Low Power Auto Set-up
Par. 22-45
Setpoint Boost
Par. 22-46
Maximum Boost Time
Par. 1-86
Trip Speed Low [RPM]
Par. 1-87
Trip Speed Low [Hz]
Par. 22-45
Setpoint Boost
Par. 22-27
Dry Pump Delay
Par. 22-46
Maximum Boost Time
Par. 22-80
Flow Compensation
Par. 22-81
Square-linear Curve Approximation
Par. 2-16
AC brake Max. Current
Par. 22-82
Work Point Calculation
Par. 22-83
Speed at No-Flow [RPM]
Par. 22-84
Speed at No-Flow [Hz]
Par. 22-85
Speed at Design Point [RPM]
Par. 22-86
Speed at Design Point [Hz]
Par. 22-87
Pressure at No-Flow Speed
Par. 22-88
Pressure at Rated Speed
Par. 22-89
Flow at Design Point
Par. 22-90
Flow at Rated Speed
1-00 Configuration Mode
Option:
Function:
[0] *
Open Loop
Motor speed is determined by applying a speed reference or by setting desired speed when in
Hand Mode.
Open Loop is also used if the frequency converter is part of a closed loop control system based
on an external PID controller providing a speed reference signal as output.
[3]
Closed Loop
Motor Speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed loop control process (e.g. constant pressure or flow). The PID controller
must be configured in parameter group 20-** or via the Function Setups accessed by pressing
the [Quick Menus] button.
This parameter cannot be changed while the motor is
running.
When set for Closed Loop, the commands Reversing
and Start Reversing will not reverse the direction of
the motor.
1-03 Torque Characteristics
Option:
Function:
[0] *
Compressor torque
Compressor
[0]: For speed control of screw and scroll compressors. Provides a voltage which is
optimized for a constant torque load characteristic of the motor in the entire range down to 10
Hz.
[1]
Variable torque
Variable Torque
[1]: For speed control of centrifugal pumps and fans. Also to be used when con-
trolling more than one motor from the same frequency converter (e.g. multiple condenser fans or
VLT HVAC Drive High Power Operating In-
structions
6 How to Programme
MG.11.F3.02 - VLT
®
is a registered Danfoss trademark
103