Enclosure
MH3
P5K5
P7K5
Overload
1)
NO
HO
NO
Typical shaft output [kW]
5.5
7.5
Typical shaft output [hp]
7.5
10
Max. cable cross-section in
terminals
2
(mains, motor)
[mm
2
/AWG]
4/10
4/10
Output current
40
°
C ambient temperature
Continuous
(3x380-440 V) [A]
12
15.5
Intermittent
(3x380-440 V) [A]
13.2
14.4
17.1
Continuous
(3x440-480 V) [A]
11
14
Intermittent
(3x440-480 V) [A]
12.1
13.2
15.4
Max. input current
Continuous
(3x380-440 V )[A]
11
15
Intermittent
(3x380-440 V) [A]
12
17
17
Continuous
(3x440-480 V) [A]
9.4
13
Intermittent
(3 x 440-480 V) [A]
10
15
14
Max. mains fuses
See
Table 6.12 Mains Supply 3x380-480 V AC Normal and High Overload: MH3 Enclosure
1) NO: Normal overload, 110% for 1 minute. HO: High overload, 160% for 1 minute
A frequency converter intended for HO requires a corresponding motor rating. For example, Table 6.12 shows that a 5.5 kW motor for HO requires
a P7K5 frequency converter.
2) Max. cable cross-section is the largest cable cross-section that can be attached to the terminals. Always observe national and local regulations.
Specifications
VLT
®
DriveMotor FCP 106 and FCM 106 Design Guide
54
MG03M102 -
08/2015
6