2.1.4 Control Terminals
195NA458.10
1
2
3
5
4
Illustration 2.5 Location of Terminals and Relays, MH1
195NA409.10
1
2
3
5
4
Illustration 2.6 Location of Terminals and Relays, MH2-MH3
1
Control terminals
2
Relays
3
UDC+, UDC-, Line (L3, L2, L1)
4
PE
5
LCP connector
Table 2.2 Legend to
Control terminals
18 19
12 20 55
27 29 42 45 50 53 54
DIGI IN
DIGI IN
DIGI IN
DIGI IN
61 68 69
N
P
COMM. GND
+24V
0/4-20mA A OUT / DIG OUT
0/4-20mA A OUT / DIG OUT
GND
GND
10V/20mA IN
10V/20mA IN
10V OUT
130BB625.10
BUS TER.
OFF
ON
Illustration 2.7 Control Terminals
Terminal
number
Function
Configuration
Factory
setting
12
+24 V output
18
Digital input *PNP/NPN
Start
19
Digital input *PNP/NPN
No operation
20
Com
27
Digital input *PNP/NPN
Coast inverse
29
Digital input *PNP/NPN
Jog
50
+10 V output
53
Analog input *0-10 V/0-20 mA/
4-20 mA
Ref1
54
Analog input *0-10 V/0-20 mA/
4-20 mA
Ref2
55
Com
42
12 bit
*0-20 mA/4-20
mA/DO
Analog
45
12 bit
*0-20 mA/4-20
mA/DO
Analog
1, 2, 3
Relay 1
1,2 NO 1,3 NC
[9] Alarm
4, 5, 6
Relay 2
4,5 NO 4,6 NC
[5] Drive
running
Table 2.3 Control Terminal Functions
* indicates default setting
Note: PNP/NPN is common for terminals 18, 19 and 27
2.1.5 Serial Communication (Fieldbus)
Networks
These protocols are embedded in the frequency converter:
•
BACnet MSTP
•
Modbus RTU
•
N2 Metasys
•
FC Protocol
Product Overview