Decentral Solutions
All About FCD
300
■
Technical data, line supply 3 x 380 - 480V
According to international
standards
Type
303
305
307
311
315
322
330
335**
Output current
I
INV.
[A]
1.4
1.8
2.2
3.0
3.7
5.2
7.0
7.6
(3 x 380 - 500 V)
I
MAX
(60s) [A]
2.2
2.9
3.5
4.8
5.9
8.3
11.2
11.4
Output power (400
V)
S
INV.
[KVA]
1.0
1.2
1.5
2.0
2.6
3.6
4.8
5.3
Typical shaft output
P
M,N
[kW]
0.37
0.55
0.75
1.1
1.5
2.2
3.0
3.3
Typical shaft output
P
M,N
[HP]
0.50
0.75
1.0
1.5
2.0
3.0
4.0
5*
Max. cable cross
section, motor
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Input current
I
L,N
[A]
1.2
1.6
1.9
2.6
3.2
4.7
6.1
6.8
(3 x 380 - 480 V)
I
L,MAX
(60s)[A]
1.9
2.6
3.0
4.2
5.1
7.5
9.8
10.2
Max. cable cross
section, power
[mm
2
/AWG]
1)
4/10
4/10
4/10
4/10
4/10
4/10
4/10
4/10
Max. pre-fuses
[IEC]/UL
2)
[A]
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
Efficiency
3)
[%]
96
Power loss at max.
load
[W]
22
29
40
59
80
117
160
190
Weight
[kg]
5.8
5.8
5.8
5.8
5.8
9.5
9.5
9.5
* At electrical voltage min 3 x 460 - 480 V
** t
amb
max. 95° F (35° C).
1. American Wire Gauge. Max. cable cross
section is the largest cable cross section that can
be attached to the terminals. Always observe
national and local regulations.
2. Typr gG / gL pre fuses or corrosponding
circuit brakers should be used.
If you want to maintain UL/cUL branch circuit fuses
according to NEC should be used. Alternatively
a circuit braker Danfoss type CTI 25 MB or
equivalent should be used.
To be placed for protection in a circuit that is capable
of supplying a maximum of 100,000 amps for
fuses / 10,000 amps for circuit brakers.
3. Measured using a 39 ft (10 m) shielded/armored
motor cable with a rated load and rated frequency.
MG.90.F2.22 - VLT is a registered Danfoss trademark
199