Illustration 4.6 Speed Reference Value
The bus speed reference has the following format:
Parameter 3-00 Reference Range
= 0 [ref
MIN
to ref
MAX
] 0
(0000 hex) [RPM] to + 32767 (7FFF hex) [RPM]
Parameter 3-00 Reference Range
= 1 [-ref
MAX
to +ref
MAX
]
-32767 (8001 hex ) to +32767 [RPM] (7FFF hex)
The actual reference [Ref. %] in the frequency converter
depends on the settings in the following parameters:
Parameter 1-23 Motor Frequency
Parameter 1-25 Motor Nominal Speed
Parameter 3-03 Maximum Reference
NOTICE
When the bus speed reference is negative, and the
control word contains a run reverse signal, the frequency
converter runs clockwise (- - is +).
Example:
Parameter 1-25 Motor Nominal Speed
= 1420 RPM
Parameter 1-23 Motor Frequency
= 50 Hz
Parameter 3-03 Maximum Reference
= 1420 RPM
To run the motor at 25%, the reference transmitted must
be: (1420x0.25) = 355 = 16.3 hex
163 hex
⇒
25%
⇒
F
out
= 12.5 Hz
4.4.4 Actual Output Speed under Instances
20/70 and 21/71
Illustration 4.7 Actual Output Speed Value
The value of the actual speed of the motor, is transmitted
in the form of a 16-bit word.
The value is transmitted as a whole number (negative
figures are formed with 2's complement).
-32767 (8000 hex) [RPM] to +32767 [RPM] (7FFF hex) [RPM]
4.5 FC Control Profile
4.5.1 Control Word under Instances
100/150, 101/151, and 102/152
To select FC protocol in the control word, set
parameter 8-10 Control Word Profile
to
[0] FC profile
. The
control word is used to send commands from a master
(PLC or PC) to a slave (frequency converter).
Illustration 4.8 Control Words in Instances 100, 101, and 102
Bit
Bit value = 0
Bit value = 1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output frequency
Use ramp
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
No function
Relay 01 active
12
No function
Relay 04 active
13
Parameter set-up
Selection lsb
14
Parameter set-up
Selection msb
15
No function
Reverse
Table 4.5 Bits in Instances 100, 101, and 102
Explanation of the control bits:
Bits 00/01
Bits 00 and 01: Select between the 4 reference values,
which are pre-programmed in
parameter 3-10 Preset
Reference
according to
.
Programmed
reference
value
Parameter
Bit 01
Bit 00
1
3-10 [0]
0
0
2
3-10 [1]
0
1
3
3-10 [2]
1
0
4
3-10 [3]
1
1
Table 4.6 Reference Values
Control
Programming Guide
MG92F102
Danfoss A/S © 12/2015 All rights reserved.
13