8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in
parameter 8-03 Control Word Timeout Time
Option:
Function:
[26] Trip
8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control
word following a timeout.
This parameter is active only when
parameter 8-04 Control Timeout Function
is set
to:
•
[7] Set-up 1
.
•
[8] Set-up 2
.
•
[9] Set-up 3
.
•
[10] Set-up 4
.
[0]
Hold set-
up
Retains the set-up selected in
parameter 8-04 Control Timeout Function
and
shows a warning until
parameter 8-06 Reset
Control Timeout
toggles. Then the frequency
converter resumes its original set-up.
[1]
*
Resume
set-up
Resumes the set-up that was active before the
timeout.
8-06 Reset Control Word Timeout
This parameter is active only when
[0] Hold set-up
has been
selected in
parameter 8-05 End-of-Timeout Function
.
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in
parameter 8-04 Control Word Timeout Function
following a control word timeout.
[1]
Do reset
Restores the frequency converter to the
original set-up following a control word
timeout. The frequency converter performs
the reset and then immediately reverts to the
[0] Do not reset
setting.
8-07 Diagnosis Trigger
This parameter has no function for DeviceNet.
Option:
Function:
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power cycle is required for changes to take effect.
Option:
Function:
[0] Motor Data
Std-Filt.
Normal fieldbus readouts.
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered, if the function is required. A
power cycle is required for changes to take effect.
Option:
Function:
[1] Motor Data
LP-Filter
Filtered fieldbus readouts of the following
parameters:
•
Parameter 16-10 Power [kW]
.
•
Parameter 16-11 Power [hp]
.
•
Parameter 16-12 Motor Voltage
.
•
Parameter 16-14 Motor current
.
•
Parameter 16-16 Torque [Nm]
.
•
Parameter 16-17 Speed [RPM]
.
•
Parameter 16-22 Torque [%]
.
•
Parameter 16-25 Torque [Nm] High
.
8-10 Control Word Profile
Instances 20/70 and 21/71 are selectable in
parameter 10-10 Process Data Type Selection
.
Option:
Function:
[0]
*
FC profile
Instances 100/150 and 101/151 are
selectable in
parameter 10-10 Process
Data Type Selection
.
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
[8]
MCO
8-13 Configurable Status Word STW
The status word has 16 bits (0–15). Bits 5 and 12–15 are config-
urable. Each of these bits can be configured to any of the
following options.
Option:
Function:
[0]
No function
The input is always low.
[1]
Profile Default
Depending on the profile set in
parameter 8-10 Control Profile
.
[2]
Alarm 68 Only
The input goes high whenever
alarm 68, Safe Stop activated
is
active, and goes low whenever
alarm 68 Safe Stop activated
is not
activate.
[3]
Trip excl Alarm 68
[10] T18 DI status
[11] T19 DI status
[12] T27 DI status
[13] T29 DI status
[14] T32 DI status
[15] T33 DI status
[16] T37 DI status
The input goes high whenever
terminal 37 has 0 V and goes low
whenever terminal 37 has 24 V.
Parameters
Programming Guide
MG92F102
Danfoss A/S © 12/2015 All rights reserved.
29