6 Specifications
6.1 Mains Supply 3x200–240 V AC
Table 19: 3x200–240 V AC
Drive
4 TR/VZH028
5 TR/VZH035
6.5 TR/VZH044
Typical shaft output [kW]
6.0
7.5
10
IP20 enclosure protection rating
H4
H4
H5
Maximum cable size in terminals (mains, compressor) [mm
2
/AWG]
16/6
16/6
16/6
Output current
Continuous (3x200–240 V) [A]
20.7
25.9
33.7
Intermittent (3x200–240 V) [A]
–
–
37.1
Maximum input current
Continuous (3x200–240 V) [A]
23
28.3
37
Intermittent (3x200–240 V) [A]
–
–
41.5
3.2.4.5 Recommendation of Fuses
Estimated power loss [W], best case/typical
(1)
182/204
229/268
369/386
Weight enclosure protection IP20 [kg/(lb)]
7.9 (17.4)
7.9 (17.4)
9.5 (21)
Efficiency [%], best case/typical
(1)
97.3/97
98.5/97.1
97.2/97.1
1
At rated load conditions.
6.2 Mains Supply 3x380–480 V AC
Table 20: 3x380–480 V AC
Drive
4 TR/VZH028
5 TR/VZH035
6.5 TR/
VZH044
13 TR/
VZH088
17 TR/
VZH117
26 TR/
VZH170
Typical shaft output [kW]
6.0
7.5
10
18.5
22.0
30.0
Typical shaft output [hp]
8.0
10
15
25
30
40
Protection rating IP20
H3
H3
H4
H5
H5
H6
Maximum cable size in
terminals (mains, motor)
[mm
2
(AWG)]
4/10
4/10
16/6
16 (6)
16 (6)
35 (2)
Output current - 40 °C (104 °F) ambient temperature
Continuous (3x380–440
V)[A]
11.6
14.3
16.4
37
44
61
Intermittent (3x380–440
V) [A]
–
–
18
40.7
46.8
67.1
Continuous (3x441–480
V) [A]
9.8
12.3
15.5
34
40
52