7.2 Electrical Data, 525–690 V
VLT
®
AutomationDrive FC 302
N55K
N75K
N90K
N110
N132
High/normal overload
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
(High overload=150% current during
60 s, normal overload=110% current
during 60 s)
Typical shaft output at 525 V [kW]
45
55
55
75
75
90
90
110
110
132
Typical shaft output at 575 V [hp]
60
75
75
100
100
125
125
150
150
200
Typical shaft output at 690 V [kW]
55
75
75
90
90
110
110
132
132
160
Enclosure size
D1h/D3h/D5h/D6h
Output current (3-phase)
Continuous (at 525 V) [A]
76
90
90
113
113
137
137
162
162
201
Intermittent (60 s overload)
(at 525 V) [A]
114
99
135
124
170
151
206
178
243
221
Continuous (at 575/690 V) [A]
73
86
86
108
108
131
131
155
155
192
Intermittent (60 s overload)
(at 575/690 V) [A]
110
95
129
119
162
144
197
171
233
211
Continuous kVA (at 525 V) [kVA]
69
82
82
103
103
125
125
147
147
183
Continuous kVA (at 575 V) [kVA]
73
86
86
108
108
131
131
154
154
191
Continuous kVA (at 690 V) [kVA]
87
103
103
129
129
157
157
185
185
230
Maximum input current
Continuous (at 525 V) [A]
74
87
87
109
109
132
132
156
156
193
Continuous (at 575/690 V)
70
83
83
104
104
126
126
149
149
185
Maximum number and size of cables per phase
- Mains, motor, brake, and load share
[mm
2
(AWG)]
2x95 (2x3/0)
2x95 (2x3/0)
2x95 (2x3/0)
2x95 (2x3/0)
2x95 (2x3/0)
Maximum external mains fuses [A]
1)
160
315
315
315
315
Estimated power loss at 575 V [W]
2), 3)
1098
1162
1162
1428
1430
1740
1742
2101
2080
2649
Estimated power loss at 690 V [W]
2), 3)
1057
1204
1205
1477
1480
1798
1800
2167
2159
2740
Efficiency
3)
0.98
0.98
0.98
0.98
0.98
Output frequency [Hz]
0–590
0–590
0–590
0–590
0–590
Heat sink overtemperature trip [
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [
°
C
(
°
F)]
75 (167)
75 (167)
75 (167)
75 (167)
75 (167)
Table 7.5 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.5 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
±
15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-
efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for
slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.11 Efficiency. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
Specifications
VLT® AutomationDrive FC 302
40
Danfoss A/S © 01/2018 All rights reserved.
MG38C202
7
7