
130BA046.11
60%
0%
100%
U
m
Changeover
f
out
Par.1-60
Par.1-61
Illustration 3.11
1-61 High Speed Load Compensation
Range:
Function:
100 %
*
[0 - 300
%]
Enter the % value to compensate voltage in
relation to load when the motor is running
at high speed and obtain the optimum U/f
characteristic. The motor size determines
the frequency range within which this
parameter is active.
Motor size
Change-over
0.25 kW - 7.5 kW
> 10 Hz
Table 3.6
1-62 Slip Compensation
Range:
Function:
Size
related
*
[-500 -
500 %]
Enter the % value for slip compensation, to
compensate for tolerances in the value of
n
M,N
. Slip compensation is calculated
automatically, i.e. on the basis of the rated
motor speed n
M,N
.
This function is not active when
is set to
[1] Speed
closed loop
or
[2] Torque
Torque control
with speed feedback or when
is set to
[0] U/f
special
motor mode.
1-63 Slip Compensation Time Constant
Range:
Function:
Size related
*
[0.05 - 5.00
s]
Enter the slip compensation reaction
speed. A high value results in slow
reaction, and a low value results in
quick reaction. If low-frequency
resonance problems arise, use a
longer time setting.
NOTE
1-63 Slip Compensation Time Constant
will not have effect
when
1-10 Motor Construction
= [1] PM, non salient SPM.
1-64 Resonance Dampening
Range:
Function:
100 %
*
[0 - 500
%]
Enter the resonance dampening value. Set
and
1-65 Resonance Dampening Time Constant
to
help eliminate high-frequency resonance
problems. To reduce resonance oscillation,
increase the value of
NOTE
will not have effect when
1-10 Motor Construction
= [1] PM, non salient SPM.
1-65 Resonance Dampening Time Constant
Range:
Function:
5 ms
*
[5 - 50 ms] Set
and
1-65 Resonance Dampening Time Constant
to
help eliminate high-frequency resonance
problems. Enter the time constant that
provides the best dampening.
NOTE
1-65 Resonance Dampening Time Constant
will not have
effect when
1-10 Motor Construction
= [1] PM, non salient
SPM.
1-66 Min. Current at Low Speed
Range:
Function:
100
%
*
[ 1. - 200. %]
Enter the minimum motor current at low
speed, see
.
Increasing this current improves motor
torque at low speed.
1-66 Min. Current at Low Speed
is enabled
when
[0] Speed
open loop
only. The frequency converter
runs with constant current through
motor for speeds below 10æHz.
For speeds above 10æHz, the motor flux
model in the frequency converter
controls the motor.
andæ/æor
automatically adjust
1-66 Min. Current at Low Speed
. The
parameter with the highest value adjusts
1-66 Min. Current at Low Speed
. The
current setting in
is composed of the torque
generating current and the magnetizing
current.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
42
MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3