Parameter 0-04 Operating State at Power-up (Hand)
Table 12: Parameter 0-04 Operating State at Power-up (Hand)
0-04 Operating State at Power-up (Hand)
Default value: [1] Forced stop, ref=old
Parameter type: Option
Setup: All setups
Conversion index: –
Data type: Uint8
Change during operation: True
Select the operating mode upon reconnection of the drive to mains voltage after power-down in hand-on mode.
Option Name
Description
[0]
Resume
Restart the drive, maintaining the start/stop settings (applied by [Hand On]/[Off]) selected before
the power-down of the drive.
[1]*
Forced stop,
ref=old
Restart the drive with a saved local reference after mains voltage reappears and after pressing
[Hand On].
[2]
Forced stop, ref=0 Reset the local reference to 0 when restarting the drive.
4.1.2 0-1* Set-up Operations
Define and control the individual parameter setups. The drive has 4 parameter setups that can be programmed independently of
each other. This makes the drive very flexible and able to solve advanced control functionality problems, often saving the cost of
external control equipment. Parameter setups can be used to program the drive to operate according to 1 control scheme in 1
setup (for example, motor 1 for horizontal movement) and another control scheme in another setup (for example, motor 2 for verti-
cal movement). Alternatively, parameter setups can be used by an OEM machine builder to identically program all their factory-
fitted drives for different machine types within a range to have the same parameters. During production/commissioning, simply
select a specific setup depending on which machine the drive is installed on.
The active setup (that is the setup in which the drive is currently operating) can be selected in
parameter 0-10 Active Set-up
and is
shown in the LCP. By using multi setup, it is possible to switch between setups with the drive running, or it can be stopped via
digital input or serial communication commands. If it is necessary to change setups while the drive is running, ensure that
parame-
ter 0-12 This Set-up Linked to
is programmed as required. By using
parameter 0-11 Edit Set-up
, it is possible to edit parameters within
any of the setups while continuing the operation of the drive in its active setup, which can be a different setup to the one being
edited. By using
parameter 0-51 Set-up Copy
, it is possible to copy parameter settings between the set-ups to enable quicker com-
missioning if similar parameter settings are required in different setups.
Use
parameter 0-51 Set-up Copy
to copy a setup to 1 or all other setups. Stop the drive before switching between setups where
parameters marked not changeable during operation have different values. To avoid conflicting settings of the same parameter
within 2 different setups, link the setups together using
parameter 0-12 This Set-up Linked to
. Parameters which are not changeable
during operation are marked FALSE in the
Change during operation
field.
Parameter 0-10 Active Set-up
Table 13: Parameter 0-10 Active Set-up
0-10 Active Set-up
Default value: [1] Set-up 1
Parameter type: Option
Setup: 1 setup
Conversion index: –
Data type: Uint8
Change during operation: True
Select the setup to control the drive functions.
Option Name
Description
[0]
Factory setup Cannot be changed. It contains the data set and can be used as a data source when returning the other
setups to a known state.
[1]*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
are the 4 separate parameter setups within which all parameters can be pro-
grammed.
[2]
Set-up 2
AU373327181955en-000101 / 130R1208 | 33
Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide