4.14.8 14-8* Options
Parameter 14-88 Option Data Storage
Table 517: Parameter 14-88 Option Data Storage
14-88 Option Data Storage
Default Value: 0
Parameter Type: Range, 0 - 65535, Array [24]
Setup: 2 set-ups
Conversion Index: 0
Data Type: Uint16
Change during operation: True
This parameter stores information about options over a power cycle.
Parameter 14-89 Option Detection
Table 518: Parameter 14-89 Option Detection
14-89 Option Detection
Default Value: [0] Protect option config.
Parameter Type: Option
Setup: 1 set-up
Conversion Index: -
Data Type: Uint8
Change during operation: True
Selects the behavior of the drive when a change in the option configuration is detected.
Option Name
Description
[0]*
Protect option config. Freezes the current settings and prevents unwanted changes when missing or defective op-
tions are detected.
[1]
Enable option change Changes drive settings and is used when modifying the system configuration. This parameter
setting returns to
[0] Protect option config.
after an option change.
4.14.9 14-9* Fault Settings
Parameter 14-90 Fault Level
Table 519: Parameter 14-90 Fault Level
14-90 Fault Level
Default Value: Size related
Parameter Type: Option, Array [26]
Setup: 1 set-up
Conversion Index: -
Data Type: Uint8
Change during operation: True
This is an array parameter with 26 elements. Each of the bits can be configured to any of the following options. Use this parameter
to customize fault levels.
Option Name
Description
[0]
Off
Use
[0] Off
with caution as it ignores all warnings and alarms for the selected source.
[1]
Warning
[2]
Trip
Changing a fault level from default option
[3] Trip Lock
to
[2] Trip
leads to the automatic reset of the
alarm. For alarms involving overcurrent, the drive has a hardware protection that issues a 3-minute re-
covery after 2 consecutive overcurrent incidents. This hardware protection cannot be overruled.
[3]
Trip lock
[4]
Trip w. de-
layed reset
This option adds a delay between automatic resets, otherwise it is the same as option
[2] Trip
. The delay
prevents a situation where reset is attempted repeatedly for an overcurrent situation. Hardware protec-
tion of the drive forces the 3-minute recovery time after 2 consecutive overcurrents (within a short time
window).
AU373327181955en-000101 / 130R1208
282 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide