P. 2-23
Down Time
p. 2-29
P. 2-24
Ramp 1 Down
P. 3-42
Ramp 1 Up
P. 3-41
Time
p. 2-25
Up Time
p. 2-27
Stop Delay Activate Brake Torque Ramp
Brake Release
Torque Ramp
Motor
speed
Torque
ref.
Brake
relay
Mech brake
feedback
Mech brake
position
Gain boost or
position control
Gain Boost p. 2-28
Contact no. 2
OPTIONAL
e.g. DI32 [70] Mech. Brake Feedback
Contact no. 1
e.g. DI32 [70] Mech. Brake Feedback
Torque ref. p. 2-26
Illustration 41: Brake Release Sequence for Hoist Mechanical Brake Control
Parameter 2-26 Torque Ref
to
parameter 2-33 Speed PID Start Lowpass Filter Time
are only available for the hoist mechanical brake
control (flux with motor feedback).
4.3.4 2-3* Adv. Mech Brake
Parameter 2-30 Position P Start Proportional Gain
to
parameter 2-33 Speed PID Start Lowpass Filter Time
can be set up for very smooth
transition change from speed control to position control during
parameter 2-25 Brake Release Time
- the time when the load is trans-
ferred from the mechanical brake to the drive.
Parameter 2-30 Position P Start Proportional Gain
to
parameter 2-33 Speed PID Start
Lowpass Filter Time
are activated when
parameter 2-28 Gain Boost Factor
is set to 0.
Parameter 2-30 Position P Start Proportional Gain
Table 172: Parameter 2-30 Position P Start Proportional Gain
2-30 Position P Start Proportional Gain
Default value:0.0000
Parameter type: Range, 0.0000 - 1.0000
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: True
Enter the position controller during start proportional gain. Quick control is obtained at high amplification. However, if the amplifi-
cation is too high, the process may become unstable.
Parameter 2-31 Speed PID Start Proportional Gain
Table 173: Parameter 2-31 Speed PID Start Proportional Gain
2-31 Speed PID Start Proportional Gain
Default value: 0.0150
Parameter type: Range, 0.0000 - 1.0000
Setup: All setups
Conversion index: -4
Data type: Uint32
Change during operation: True
Enter the speed controller proportional gain during start. Quick control is obtained at high amplification. However, if amplification is
too high, the process may become unstable.
AU373327181955en-000101 / 130R1208
106 | Danfoss A/S © 2021.08
Parameter Descriptions
VLT® AutomationDrive EZ FC 321
Programming Guide