4.10 Parameters: 9-** PROFIdrive
9-00 Setpoint
Range:
Function:
0
*
[0 -
65535 ]
This parameter receives cyclic reference from a
Master Class 2. If the control priority is set to
Master Class 2, the reference for the frequency
converter is taken from this parameter, whereas
the cyclical reference is ignored.
9-07 Actual Value
Range:
Function:
0
*
[0 - 65535 ] This parameter delivers the MAV for a Master
Class 2. The parameter is valid if the control
priority is set to Master Class 2.
9-15 PCD Write Configuration
Select the parameters to be assigned to PCD 3–10 of the
telegrams. The number of available PCDs depends on the
telegram type. Values in PCD 3–10 are written to the selected
parameters as data. For standard PROFIBUS telegrams, see
parameter 9-22 Telegram Selection
Option:
Function:
[0]
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp Up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp Up Time
[352]
Ramp 2 Ramp Down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[412]
Motor Speed Low Limit [Hz]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
[553]
Term. 29 High Ref./Feedb. Value
[558]
Term. 33 High Ref./Feedb. Value
[590]
Digital & Relay Bus Control
[593]
Pulse Out 27 Bus Control
[595]
Pulse Out 29 Bus Control
[615]
Terminal 53 High Ref./Feedb.
Value
[625]
Terminal 54 High Ref./Feedb.
Value
[696]
Terminal 42 Output Bus Control
[748]
PCD Feed Forward
[890]
Bus Jog 1 Speed
[891]
Bus Jog 2 Speed
[1680]
Fieldbus CTW 1
[1682]
Fieldbus REF 1
[3401]
PCD 1 Write For Application
[3402]
PCD 2 Write For Application
9-15 PCD Write Configuration
Select the parameters to be assigned to PCD 3–10 of the
telegrams. The number of available PCDs depends on the
telegram type. Values in PCD 3–10 are written to the selected
parameters as data. For standard PROFIBUS telegrams, see
parameter 9-22 Telegram Selection
.
Option:
Function:
[3403]
PCD 3 Write For Application
[3404]
PCD 4 Write For Application
[3405]
PCD 5 Write For Application
[3406]
PCD 6 Write For Application
[3407]
PCD 7 Write For Application
[3408]
PCD 8 Write For Application
[3409]
PCD 9 Write For Application
[3410]
PCD 10 Write For Application
9-16 PCD Read Configuration
Select the parameters to be assigned to PCD 3–10 of the
telegrams. The number of available PCDs depends on the
telegram type. Values in PCD 3 to 10 contain the actual data
values of the selected parameters.
Option:
Function:
[0]
[1500]
Operating hours
[1501]
Running Hours
[1502]
kWh Counter
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference [%]
[1603]
Status Word
[1605]
Main Actual Value [%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor current
[1615]
Frequency [%]
[1616]
Torque [Nm]
[1618]
Motor Thermal
[1622]
Torque [%]
[1630]
DC Link Voltage
[1633]
Brake Energy /2 min
[1634]
Heatsink Temp.
[1635]
Inverter Thermal
[1638]
SL Controller State
[1639]
Control Card Temp.
[1650]
External Reference
[1652]
Feedback[Unit]
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
[1661]
Terminal 53 Setting
[1662]
Analog Input 53
Parameter Descriptions
VLT
®
AutomationDrive FC 360
78
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4
4