Time
REF
Min
Speed
ON
Time
Time
OFF
ON
OFF
Start
Stop
130BA251.10
Speed
Illustration 3.28 Bypass Valve Control
Principle
[199] Pipe Filling
Active when the pipe fill function is
operating. See
parameter group 29-** Water
Application Functions
.
The below setting options are all related to
the cascade controller.
See
parameter group 25-** Cascade
Controller
for more details.
[200] Full Capacity
All pumps running at full speed.
[201] Pump1
Running
One or more of the pumps controlled by
the cascade controller are running. The
function also depends on the setting in
parameter 25-05 Fixed Lead Pump
. If set to
[0] No
, Pump 1 refers to the pump
controlled by relay1, and so on. If set to
[1]
Yes
, Pump 1 refers to the pump controlled
by the frequency converter only (without
any of the built-in relays involved) and
Pump 2 to the pump controlled by relay1.
See
.
[202] Pump2
Running
See [201].
[203] Pump3
Running
See [201].
[204] Pump 4
running
[205] Pump 5
running
[206] Pump 6
running
[207] Pump 7
running
[208] Pump 8
running
[209] Pump 9
running
[240] RS Flipflop 0
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[241] RS Flipflop 1
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[242] RS Flipflop 2
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[243] RS Flipflop 3
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[244] RS Flipflop 4
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[245] RS Flipflop 5
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[246] RS Flipflop 6
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
[247] RS Flipflop 7
See
parameter 13-15 RS-FF Operand S
,
parameter 13-16 RS-FF Operand R
.
Setting in
parameter group
5-3* Digital Outputs
Setting in
[0] No
[1] Yes
[201] Pump 1
Running
Controlled by
relay1
Controlled by
frequency converter
[202] Pump 2
Running
Controlled by
relay2
Controlled by
relay1
[203] Pump 3
Running
–
Controlled by
relay2
Table 3.15 Pumps Controlled by the Cascade Controller
5-30 Terminal 27 Digital Output
This parameter has the options described in
.
Option:
Function:
[0]
*
No operation
5-31 Terminal 29 Digital Output
This parameter has the options described in
.
Option:
Function:
[0]
*
No operation
5-32 Term X30/6 Digi Out (MCB 101)
This parameter has the options described in
.
Option:
Function:
[0]
*
No operation This parameter is active when VLT
®
General
Purpose I/O MCB 101 is mounted in the
frequency converter.
5-33 Term X30/7 Digi Out (MCB 101)
Option:
Function:
[0]
*
No operation This parameter is active when VLT
®
General
Purpose I/O MCB 101 is mounted in the
frequency converter. Same options and
functions as
parameter group 5-3* Digital
Inputs
.
Parameter Description
VLT
®
AQUA Drive FC 202
84
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3