NOTICE
Options
[4] PTC 1 Alarm
to
[9] PTC 1 & Relay W/A
are only
available when the MCB 112 is connected.
NOTICE
Selecting
Auto Reset/Warning
enables automatic restart
of the frequency converter.
Function
Num
-
ber
PTC
Relay
No Function
[0]
–
–
Safe Torque Off
Alarm
[1]*
–
Safe Torque Off
[A68]
Safe Torque Off
Warning
[3]
–
Safe Torque Off
[W68]
PTC 1 Alarm
[4]
PTC 1 Safe Torque
Off [A71]
–
PTC 1 Warning
[5]
PTC 1 Safe Torque
Off [W71]
–
PTC 1 & Relay A
[6]
PTC 1 Safe Torque
Off [A71]
Safe Torque Off
[A68]
PTC 1 & Relay W
[7]
PTC 1 Safe Torque
Off [W71]
Safe Torque Off
[W68]
PTC 1 & Relay A/W [8]
PTC 1 Safe Torque
Off [A71]
Safe Torque Off
[W68]
PTC 1 & Relay W/A [9]
PTC 1 Safe Torque
Off [W71]
Safe Torque Off
[A68]
Table 3.14 Overview of Functions, Alarms, and Warnings
W means warning and A means alarm. For further information, see
Alarms and Warnings in chapter 5 Troubleshooting.
A dangerous failure related to Safe Torque Off issues
alarm
72, Dangerous failure
.
Refer to
.
5-20 Terminal X46/1 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-21 Terminal X46/3 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-22 Terminal X46/5 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-23 Terminal X46/7 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-24 Terminal X46/9 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-25 Terminal X46/11 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
5-26 Terminal X46/13 Digital Input
This parameter is related to the digital input on VLT
®
Extended
Relay Card MCB 113. The parameter contains all options and
functions listed in
parameter group 5-1* Digital Inputs
except for
option
[32] Pulse input
.
3.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
parameter 5-01 Terminal 27 Mode
and set the
I/O function for terminal 29 in
.
NOTICE
These parameters cannot be adjusted while the motor is
running.
The digital outputs can be programmed
with these functions:
[0]
No operation
Default for all digital outputs and relay
outputs.
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3]
Drive ready/
remote
control
The frequency converter is ready for
operation and is in auto-on mode.
[4]
Standby/no
warning
The frequency converter is ready for
operation. No start or stop command has
been given (start/disable). There are no
warnings.
[5]
Running
Motor is running.
[6]
Running/no
warning
The output speed is higher than the speed
set in
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
81
3
3