
3.4 Parameters 2-** Brakes
3.4.1 2-0* DC brakes
Parameter group for configuring the DC brake and DC hold
functions.
2-00 DC Hold/Preheat Current
Range:
Function:
50
%
*
[ 0 -
160 %]
NOTICE
Parameter 2-00 DC Hold/Preheat Current
is
not effective when
=
[1] PM, non-salient SPM
.
NOTICE
The maximum value depends on the rated
motor current.
Avoid 100% current for too long. It may
damage the motor.
Enter a value for holding current as a percentage
of the rated motor current I
M,N
set in
. 100% DC hold
current corresponds to I
M,N
.
This parameter holds the motor (holding torque)
or preheats the motor.
This parameter is active if
[1] DC hold/Preheat
is
selected in
parameter 1-80 Function at Stop
.
2-01 DC Brake Current
Range:
Function:
50
%
*
[ 0 -
1000 %
]
NOTICE
The maximum value depends on the rated
motor current. Avoid 100% current for too
long. It may damage the motor.
Enter a value for current as a percentage of the
rated motor current I
M,N
, see
. 100% DC brake current corresponds to
I
M,N
.
DC brake current is applied on a stop command,
when the speed is lower than the limit set in:
•
Parameter 2-03 DC Brake Cut In Speed
[RPM]
.
•
Parameter 2-04 DC Brake Cut In Speed
[Hz]
, when the DC brake inverse function
is active, or via the serial communication
port.
The braking current is active during the time
period set in
parameter 2-02 DC Braking Time
2-02 DC Braking Time
Range:
Function:
10 s
*
[0 - 60 s] Set the duration of the DC brake current set in
parameter 2-01 DC Brake Current
, once
activated.
2-03 DC Brake Cut In Speed [RPM]
Range:
Function:
Size
related
*
[ 0 - 0
RPM]
NOTICE
Parameter 2-03 DC Brake Cut In Speed
[RPM]
is not effective when
parameter 1-10 Motor Construction
=
[1] PM, non-salient SPM
.
Set the DC brake cut-in speed to activate
the DC brake current set in
parameter 2-01 DC Brake Current
after a
stop command.
When
parameter 1-10 Motor Construction
is
set to
[1] PM non-salient SPM
, this value is
limited to 0 RPM (OFF).
2-04 DC Brake Cut In Speed [Hz]
Range:
Function:
0.0 Hz
*
[0.0 - par.
4-14 Hz]
NOTICE
Parameter 2-04 DC Brake Cut In Speed
[Hz]
is not effective when
parameter 1-10 Motor Construction
=
[1] PM, non-salient SPM
.
Set the DC brake cut-in speed for activation
of the DC brake current set in
parameter 2-01 DC Brake Current
after a stop
command.
2-06 Parking Current
Range:
Function:
50
%
*
[ 0 -
1000 %]
NOTICE
Parameter 2-06 Parking Current
and
: Only active
if
[1] PM, non-salient SPM
is selected in
parameter 1-10 Motor Construction
.
Set current as percentage of rated motor
current,
. Active
with
. The parking
current is active during the time period set in
.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
63
3
3
Summary of Contents for VLT AQUA Drive FC 202
Page 2: ......