90
615
Fault Log: Error Code
(F. LOG: ERROR CODE)
Value:
[Index 1-10] Error Code: 0 - 99
Function:
This parameter makes it possible to see the reason why a fault trip
occurs. Ten log values, indicated as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value;
the highest log number [10] contains the oldest data value.
If there is a fault trip, it is possible to see its cause, the time and possibly
the values or output current or output voltage. See the section on
Warnings and Alarms for a table explaining the error codes.
Description of choice:
The fault log is only reset after manual initialization.
616
Fault Log: Time
(F. LOG: TIME)
Value:
[Index 1-10] Hours: 0 - 130,000.0
Function:
This parameter makes it possible to see the total number of hours run in
connection with the 10 most recent fault trips. Ten log values, indicated
as [1] through [10] are stored.
The lowest log number [1] contains the most recently saved data value:
the highest log number [10] contains the oldest data value.
Description of choice:
The fault log is only reset after manual initialization.
617
Fault Log: Value
(F. LOG: VALUE)
Value:
[Index 1 - 10] Value: 0 - 9999
Function:
This parameter makes it possible to see the value at which a fault trip
occurred. The unit of the value depends on the alarm active in
parameter 615, Fault Log: Error Code.
Description of choice:
The fault log is only reset after manual initialization.
618
Reset of kWh Counter
(RESET KWH COUNT)
Value:
★
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 602, kWh Counter.
Description of choice:
If Reset has been selected and the OK key is pressed, the kWh counter
of the drive is reset. This parameter cannot be selected via the serial
port.
619
Reset of Hours Run Counter
(RESET RUN. HOUR)
Value:
★
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of parameter 601, Hours Run.
Description of choice:
If Reset has been selected and the OK key is pressed, parameter 601
Hours-run is reset to zero. This parameter cannot be selected via the
serial port.
620
Operating Mode (OPERATION MODE)
Value:
★
Normal function (NORMAL OPERATION)
[0]
Function with deactivated inverter
(OPER. W/INVERT.DISAB)
[1]
Control card test (CONTROL CARD TEST)
[2]
Initialization (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter can be used for two
different tests.
It is possible to reset to the default factory settings for all Setups, except
parameters 500, Address; 501 Baud Rate; 600-605, Operating Data;
and 615-617, Fault Log.
Description of choice:
Normal function is used for normal operation of the motor.
Function with deactivated inverter is selected to operate the control
card using its control signals without running the motor.
Control card test is used to test the analog and digital inputs, analog
and digital outputs, relay output and the power supplies of the control
card.
✭
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.