24
The table below gives the operating data options for the first and
second lines of the display.
Data Item:
Unit:
Resulting reference, %
%
Resulting reference unit chosen in par. 415
Frequency
Hz
% of maximum output frequency
%
Motor current
A
Power
kW
Power
HP
Output energy
kWh
Hours run
hours
User defined readout unit chosen in par. 006
Setpoint 1 unit chosen in par. 415
Setpoint 2 unit chosen in par. 415
Feedback 1 unit chosen in par. 415
Feedback 2 unit chosen in par. 415
Feedback unit chosen in par. 415
Motor voltage
V
DC link voltage
V
Thermal load on motor
%
Thermal load on VLT
%
Input status, digital input
binary code
Input status, analog terminal 53
V
Input status, analog terminal 54
V
Input status, analog terminal 60
mA
Pulse reference
Hz
External reference
%
Heat sink temperature
o
C
Display Mode I:
Below is an example of Display Mode I, in which the drive is running in
setup 1, in Auto mode, with remote reference, at an output frequency of
40 Hz.
The text in line 1, FREQUENCY, describes the meter shown in line 2.
Line 2 shows the current output frequency (40.0Hz), direction of
rotation (reverse), and active setup (1).
SETUP
1
80.0% 5.08A
2.15kW
AUTO REMOTE RUN
40.0Hz
HAND
OFF
STOP
RAMPING
JOGGING
.
.
.
.
STAND BY
LOCAL
SETUP
1
FREQUENCY
AUTO REMOTE RUN
40.0Hz
50.0Hz
SETUP
1
100% 7.8A 5.9kW
AUTO REMOTE RUN
Line 4 is the status line and the information is automatically generated
for display by the drive in response to its operation. It shows that the
drive is in auto mode, with remote reference, and that the motor is
running. Some possible displays of the status line are shown below.
The left part of the status line indicates where the drive Run/Stop
command is from, and whether it is on or off. AUTO means that Run/
Stop control is via the control terminals and/or serial interface; HAND
indicates that the drive started locally by the Hand Start key. OFF
means that the drive ignores all control commands and the motor will
not run.
The center part of the status line indicates the reference source that is
active. REMOTE means that the reference is from the control terminals.
LOCAL indicates that the reference is determined by the + and - keys
on the control panel.
The right part of the status line indicates the drive’s operational status.
Display Mode II:
This display mode makes it possible to have three meters displayed at
the same time on line 1. The meters displayed are selected through
parameters 008, 009 and 010.