VLT
®
6000 HVAC
112
★
= factory setting. ( ) = display text [ ] = value for use in communication via serial communication port
MG.60.B1.02 - VLT is a registered Danfoss trade mark
■
■
■
■
■
Feedback signals in open loop
Normally, feedback signals and thus feedback
parameters are only used in
Closed loop
operation; in
VLT 6000 HVAC units, however, the feedback
parameters are also active in
Open loop
operation.
In
Open loop mode
, the feedback parameters can be
used to show a process value in the display. If the
present temperature is to be displayed, the
temperature range can be scaled in parameters 413/
414
Minimum/Maximum feedbac
k, and the unit (°C,
°F) in parameter 415
Process units
.
413 Minimum feedback, FB
MIN
(MIN. FEEDBACK)
Value:
-999,999.999 - FB
MAX
★
0.000
Function:
Parameters 413
Minimum feedback, FB
MIN
and 414
Maximum feedback, FB
MAX
are used to scale the
display indication, thereby ensuring that it shows the
feedback signal in a process unit proportionally to the
signal at the input.
Description of choice:
Set the value to be shown on the display at minimum
feedback signal value (par. 309, 312, 315
Min.
scaling
) on the selected feedback input (parameters
308/311/314
Analogue inputs
).
414 Maximum feedback, FB
MAX
(MAX. FEEDBACK)
Value:
FB
MIN
- 999,999.999
★
100.000
Function:
See the description of par. 413
Minimum feedback,
FB
MIN
.
Description of choice:
Set the value to be shown on the display when
maximum feedback (par. 310, 313, 316
Max. scaling
)
has been achieved at the selected feedback input
(parameters 308/311/314
Analogue inputs
).
415 Units relating to closed loop
(REF. / FDBK. UNIT)
Value:
No unit
[0]
°C
[21]
★
%
[1]
GPM
[22]
rpm
[2]
gal/s
[23]
ppm
[3]
gal/min
[24]
pulse/s
[4]
gal/h
[25]
l/s
[5]
lb/s
[26]
l/min
[6]
lb/min
[27]
l/h
[7]
lb/h
[28]
kg/s
[8]
CFM
[29]
kg/min
[9]
ft
3
/s
[30]
kg/h
[10]
ft
3
/min
[31]
m
3
/s
[11]
ft
3
/h
[32]
m
3
/min
[12]
ft/s
[33]
m
3
/h
[13]
in wg
[34]
m/s
[14]
ft wg
[35]
mbar
[15]
PSI
[36]
bar
[16]
lb/in
2
[37]
Pa
[17]
HP
[38]
kPa
[18]
°F
[39]
mVS
[19]
kW
[20]
Function:
Selection of unit to be shown on the display.
This unit will be used if
Reference [unit]
[2] or
Feedback [unit]
[3] has been selected in one of the
parameters 007-010, as well as in the Display mode.
In
Closed loop
, the unit is also used as a unit for
Minimum/Maximum reference
and
Minimum/
Maximum feedback
, as well as
Setpoint 1
and
Setpoint 2
.
Description of choice:
Select the required unit for the reference/feedback
signal.