
514
Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (off)
[0]
Freeze output frequency (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
In this parameter you can select the required reaction
for the frequency converter when the preset time in
parameter 513
Bus time interval
has been exceeded.
If choices [1] to [5] are activated the output relay will
be deactivated.
Description of choice:
The output frequency of the frequency converter can
be frozen at the present value, stop the motor, be fro-
zen at parameter 213
Jogging frequency
, be frozen at
parameter 202
Output frequency, high limit f
MAX
or stop
and activate a cut out.
515-544 Data readout
Value:
Par.
no.
Description
Display text
Unit
Update
interval
515
Res. reference
(REFERENCE %)
%
516
Res. reference [Unit]
(REFERENCE [UNIT])
Hz, rpm
517
Feedback [Unit]
(FEEDBACK [UNIT])
Par. 416
518
Frequency
(FREQUENCY)
Hz
519
Frequency x scale
(FREQUENCY X SCALE)
Hz
520
Motor current
(MOTOR CURRENT)
Amp
521
Torque
(TORQUE)
%
522
Power[kW]
(POWER (KW))
kW
523
Power[HP]
(POWER (HP))
HP
524
Motor voltage
(MOTOR VOLTAGE)
V
525
DC-link voltage
(DC LINK VOLTAGE)
V
526
Thermal load motor
(MOTOR THERMAL)
%
527
Thermal load inverter
(INV. THERMAL)
%
528
Digital input
(DIGITAL INPUT)
Bin
529
Term.53, analogue input
(ANALOG INPUT 53)
V
531
Term.60, analogue input
(ANALOG INPUT 60)
mA
532
Pulse reference
(PULSE REFERENCE)
Hz
533
External ref.
(EXT. REF.%)
%
534
Status word, Hex
(STATUS WORD)
Hex
535
Bus feedback 1
(BUS FEEDBACK1)
Hex
537
Inverter temperature
(INVERTER TEMP.)
°C
538
Alarm word
(ALARM WORD)
Hex
539
Control word
(CONTROL WORD)
Hex
540
Warning word
(WARN. WORD)
Hex
541
Extended status word
(STATUS WORD)
Hex
544
Pulse count
(PULSE COUNT)
Function:
These parameters can be read out via the serial com-
munication port and the LCP display. See also param-
eters 009-012
Display readout
.
NB!
Parameters 515-541 can only be read out
via an LCP control unit.
= factory setting, () = display text, [] = value for use in communication via serial communication port
126
MG.27.E2.02 - VLT is a registered Danfoss trademark