16
★
= ROM default setting. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
Programming
VLT
®
Series 2000
Group 0 -- Operation and Display
000 Language (LANGUAGE)
Value:
★
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Function and Description:
Determines the language of the display.
You can choose between
English, German, French and
Danish.
001 Menu Setup Select (MENU SETUP)
Value:
★
Setup 1 (SETUP 1)
[1]
Setup 2 (SETUP 2)
[2]
Multi-setup (MULTI SETUP)
[5]
Setup
Terminal 29
1
0
2
1
Function:
You can select a menu setup which is different from the
factory setting and store it in
Setup 1 or Setup 2.
Description:
You start by selecting the setup you want to make or alter.
You can choose between
Setup 1 or setup 2. Then you can
alter any data value you like. Your alterations make a setup
different from the factory setting. If you choose
Multi-setup
you can switch between the two setups via terminal 29. The
parameters which can be chosen for the two setups have
been specially selected. Refer to the Parameter/Default
Settings chart in the back of this manual.
002 Setup Copy
(
(MENU SET COPY)
Value
★
No copying (DO NOT COPY)
[0]
Copy setup 1 to 2 (COPY 1 TO 2)
[6]
Copy to 2 to 1 (COPY 2 TO 1)
[7]
Copy from fact. setting to 1 (Fact. setting
➔
1) [8]
Copy from fact. setting to 2 (Fact. setting
➔
2) [9]
Function:
You can copy
Setup 1 to Setup 2 and vice versa. You can
always copy the factory setting back to
Setup 1 or Setup 2.
Description:
The copying starts when you have entered the desired
copying function and Data mode is left by pressing the
“Menu” key, or after 20 seconds of no activity. Line 3 in the
display flashes while copying is in progress. Time out does
not activate the copying function.
003 Operation Site (LOCAL /REMOTE)
Value:
★
Remote (REMOTE)
[0]
Local with external stop (LOC/EXT./STOP)
[1]
Local (LOCAL)
[2]
Local and remote (LOCAL - REMOTE)
[3]
Function:
You can choose four different operation sites:
Remote,
Local with external stop, Local and Local and remote.
Description:
If you choose
Remote, you can control the adjustable
frequency drive via the control terminals. However, you can
still use the stop key of the control panel (provided you
have not chosen to disable this function in parameter (007).
If you choose
Local with external stop you must disconnect
the connection between terminals 12 and 27 to activate
stop.
Local with external stop can only be chosen if Motor
coasting, Quick stop, Reset and motor coasting or Stop
have been chosen in parameter 404 (terminal 27).
Choose
Local if you want to operate the unit via the
keyboard (must be activated in parameter 007).
Local and
remote adds local and external reference. This function is
selected for access to local reference even when the unit is
operated remotely.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com