MG.20.B6.02 – VLT is a registered Danfoss trademark
VLT
®
2000 Series
96
1 x 220/230/240 V
3 x 208/220/230/240 V
l
PEAK
I² xt
VLT 2010
1
32 A
4.1 A² s
VLT 2015
1
80 A
15.2 A² s
VLT 2020
1
80 A
26 A² s
VLT 2030
1
160 A
36 A² s
VLT 2040
2
16 A
4 A² s
VLT 2050
2
16 A
4 A² s
Special conditions
■
Cut-in current
On cutting in the VLT frequency converter to the
mains a cut-in current surge occurs. The cut-in
current is limited by an NTC resistor. The size of this
current surge depends on the mains impedance and
the NTC resistor’s cooling time since the last cut-in.
The current surge can be doubled if the VLT
frequency converter is still warm. The cooling time is
100-200 seconds.
Maximum cut-in current surge measured at 25°C:
3 x 308-460 V
l
PEAK
I² xt
VLT 2020
28.8 A
0.11 A² s
VLT 2025
28.8 A
0.11 A² s
VLT 2030
94.4 A
14.4 A² s
VLT 2040
94.4 A
14.4 A² s
VLT 2050
136 A
25.4 A² s
VLT 2060
136 A
25.4 A² s
1
) Single phase installation
2
) Three phase installation