Fan Size 

Item Number 

20x20mm 

1E51590C 

90x90mm 

1E250102C 

120mmx120mm 

1E51335C 

  

b.

 

Water cooled systems 

Unplug the water pump and restart the compressor to confirm the compressor will 
now run.   
If  the  system  now  runs  it  means  the  pump  is  drawing  more  than  1  Amp.   The 
system should be set up with the pump connected via a relay or pump interface to 
prevent this happening.   

 

If  it  is  not,  add  a  relay  to  the  system  or  contact  Penguin  Refrigeration  for 
further details.   

 

If there is a relay/pump interface already fitted it may have developed a fault.  
Again please contact Penguin Refrigeration for further details.      

3  Flashes  Compressor Start Error 

This  could  still  be  a  voltage  error,  due  to  a  power  surge  or  similar,  or  a  faulty 
compressor controller.   
First turn off the power to the unit for 1 minute to let the system reset.   Turn the 
power back on and see if the fridge runs. 
If the system still fails to start either: 

Return the control box to Penguin Refrigeration for testing  
Replace electronic controller: 1E50895 

http://www.penguinfrigo.co.uk/products/Electronic_Unit_for_Danfoss_BD35_Compressors-185-37.html

  

 

  

4  Flashes  Compressor Overload 

Send  the  controller  to  Penguin  Refrigeration  for  testing,  or  contact  our  technical 
team for further assistance.    

5  Flashes  Compressor Overload 

Send  the  controller  to  Penguin  Refrigeration  for  testing,  or  contact  our  technical 
team for further assistance.  