4.28.4 PWM Removal and Installation on page 228
l
l
4.26.4 Serial Driver Removal and Installation on page 218
32. Apply the compressor power.
33. Verify the +17V, +15, +5 and -15 VDC test points on the Backplane.
l
If all voltages are /- 10%, all supply voltages are good
l
If any of these voltages are not /- 10%, refer to Section 5.5.2 Determining the Cause of an
Energy Drain.
5.5.2 Determining the Cause of an Energy Drain
5.5.2.1 Determining if Serial Driver is Draining Energy
1. Remove the Service Side Cover. Refer to Section 4.1.3.1 Service Side Cover Removal and Installation on
2. Test the Backplane voltages at the +24V, +15, +5, and -15 VDC test points.
l
If all voltages are /- 10%, the Serial Driver is not draining energy
l
If any of these voltages are not /- 10%), proceed to Step 3
3. Isolate the compressor power as described in the Section 1.8 Electrical Isolation on page 22.
4. Wait for the LEDs on the Backplane to turn off.
5. Remove the Serial Driver.
6. Re-apply the compressor power.
7. Test the Backplane voltages at the +24V, +15, +5, and -15 VDC test points.
l
If all voltages are /- 10%, the Serial Driver is draining energy
l
If any of these voltages are not /- 10%, another component is draining energy
5.5.2.2 Determining if BMCC is Draining Energy
1. Remove the Service Side Cover. Refer to Section 4.1.3.1 Service Side Cover Removal and Installation on
2. First, follow the procedure in Section 5.5.2.1 Determining if Serial Driver is Draining Energy.
3. Isolate the compressor power as described in the Section 1.8 Electrical Isolation on page 22.
4. Wait for the LEDs on the Backplane to turn off.
5. Remove the Serial Driver. Refer to Section 4.26.4 Serial Driver Removal and Installation on page 218.
6. Re-apply the compressor power and test the Backplane voltages at the +24V, +15, +5, and -15 VDC test
points.
l
If all voltages are within (+/- 10%) the BMCC is not draining energy
l
If any of these voltages are not within (+/- 10%) proceed to Step 5
7. Isolate the compressor power as described in the Section 1.8 Electrical Isolation on page 22.
8. Wait for the LEDs on the Backplane to turn off.
9. Remove the BMCC (refer to Section 4.27 BMCC on page 220).
10. Re-apply the compressor power.
11. Test the Backplane voltages at the +24V, +15, +5, and the -15 VDC test points.
l
If all voltages are within (+/- 10%) the BMCC is draining energy
l
If any of these voltages are not within (+/- 10%) another component is draining energy
M-SV-001-EN Rev. H-1/23/2023 Page 271 of 294
Summary of Contents for Turbocor TT Series
Page 2: ...THIS PAGE INTENTIONALLY LEFT BLANK Page 2 of 294 M SV 001 EN Rev H 1 23 2023...
Page 14: ...Page 14 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...Page 16 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 18: ...Figure 1 2 New Type Code Page 18 of 294 M SV 001 EN Rev H 1 23 2023...
Page 46: ...Page 46 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 250: ...Page 250 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 268: ...Figure 5 3 Bearing Calibration Flow Page 268 of 294 M SV 001 EN Rev H 1 23 2023...
Page 274: ...Page 274 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 286: ...Page 286 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 290: ...Page 290 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 292: ...Page 292 of 294 M SV 001 EN Rev H 1 23 2023 THIS PAGE INTENTIONALLY LEFT BLANK...