4
The wallplate must be securely mounted either directly to
the wall using suitable wood screws or to a fl ush mounted
1-gang electrical accessory box using M3.5 screws.
Cable access can either be from behind for concealed
cabling, or from below for surface cabling. If surface cable
is used, cut out cable access slot on plug-on module prior
to mounting the module.
For wiring connections refer to diagram on page 5.
TS715-Si models are double insulated and do not require
an earth connection, however a parking terminal is
provided on the wallplate. This is clearly marked with an
Earth symbol.
Prior to mounting the plug-on module, DIL switches on
the rear of the plug-on module must be set. See diagram
on page 5 for available options.
Mount plug-on module to wallplate by locating tabs on
top of wallplate in apertures on rear of module, hinge
down and press fi rmly to wallplate before tightening
securing screws on bottom of wallplate.
Installa
tion and
W
iring
Wiring (
For Wiring Conversion tables see pages 8-11)
COM
OFF
ON
230 V
fused 3A
T
S
715 (3066 12/01)
Always switch off mains fi rst and never fi t programmer
to a live wallplate.
NOTE:
Link terminals L
and 1 for standard
mains voltage
operated systems
On 24 volt models
power supply must
be wired to A & B on
wallplate.