3
Thermostat Features
TP7000-RF
TP7000
TP7000A
TP7000-M
TP7000-MA
TP7000-M 24
Power supply
2 x AA/MN1500/LR6
alkaline batteries
230v, 50 Hz
24v, 50 Hz
Memory backup
Capacitor during
battery change for 1
minute
Rechargable cell, 24 hrs (*1)
Switching action of output relay
N/A
1 x SPDT, Type 1B
Switch rating of relay contact,
voltage and current
N/A
3(1) A, 10-230 volts
Transmitter frequency (RF only)
433.92 MHz
N/A
Transmitter range (RF only)
30m max.
N/A
Rated Impulse Voltage
N/A
2.5Kv
Dimensions (mm)
138 wide x 88 high x 28 deep
Ball Pressure Test
75°C
Temperature Range
5-30°C
Design Standard
EN 60730-2-7 (EN300220 for RF)
Control Pollution Situation
Degree 2
Time accuracy
± 1 min.
Temperature accuracy
±1°C
*1: Unit must powered up for 6 days to charge cell before full back-up is available
Installation Instructions
Important note RF products:
Ensure that there are no large metal objects,
such as boiler cases or other large appliances, in line of sight between the
transmitter and receiver as these will prevent communication between
thermostat and receiver.
Specifi cation
Installa
tion Instruc
tions
Please Note:
This product should only be installed by a qualifi ed electrician
or competent heating installer and should be in accordance with
the current edition of the IEEE wiring regulations.
GB