![background image](http://html1.mh-extra.com/html/danfoss/tp5001-series/tp5001-series_installation-manual_3830382009.webp)
9
Option 34 - Select On/Off or chrono-proportional
This allows the thermostat to be set to run in On/Off
mode or for a chrono-proportional cycle rate to be
selected. Press
+
until Option 34 is displayed, use
V
and
Λ
to select required setting.
0
On/Off
3
3 cycles per hour
6
6 cycles per hour (factory setting)
9
9 cycles per hour
12
12 cycles per hour
Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12)
(seek advice prior to adjusting)
This adjusts the integration time of the PI
algorithm to increase control accuracy. It should
only be adjusted after seeking advice from the
manufacturer. Press
+
until Option 35 is displayed,
use
V
and
Λ
to select required setting.
2.5
Integration time set to 2.5% (factory setting)
5
Integration time set to 5%
10
Integration time set to 10%
Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press
+
until Option 36 is
displayed, use
V
and
Λ
to select required setting.
Setting 0
No limit (factory setting)
Setting 1
Limited to ±2°C
Setting 2
No override allowed
Installa
tion Instruc
tions
GB
Summary of Contents for TP5001 series
Page 40: ...40 RF TP5001 TP5001 RF TP5001M 2 5 75 C 2 1 C 1 15 15 30 100 UA...
Page 41: ...41 TP5001 1 2 3 L N D E S1 S2 A M 230 1 5 2 DIL 1 2 UA...
Page 42: ...42 TP5001 TP5001 TP5001 TP5001A TP5001MA 1 2 3 TP5001 TP5001 RF RESET D E UA...
Page 45: ...45 RX3 1 1 3 5 2 1 2 PROG CH2 RX2 5 3 1 2 PROG CH3 RX3 5 TP5001 RF V TP5001 TP5001 UA...
Page 46: ...46 a V PROG 3 b V PROG 5 c V d RUN PROG UA...
Page 47: ...47 30 30 V 40 5 C 30 C 31 31 V 5 40 C 5 C 32 32 V 0 1 33 33 V 0 1 UA...
Page 48: ...48 34 34 V 0 3 3 6 6 9 9 12 12 35 34 3 6 9 12 PI 35 V 2 5 2 5 5 5 10 10 36 36 V 0 1 2 C 2 UA...
Page 49: ...49 38 38 V 0 1 37 36 1 2 37 V 0 1 1 2 2 3 3 4 4 40 2 4 6 40 V 1 2 4 6 UA...
Page 50: ...50 70 DIL 1 70 V 0 1 71 24 230 2 90 71 V 0 1 41 5 2 24 5 2 24 41 V 5 2 5 2 24 24 UA...
Page 52: ...52 90 A 90 V 0 1 2 93 3 94 93 A 90 2 93 V 2 C F10 20 50 C 27 C UA...
Page 53: ...53 94 A 90 3 94 V 0 1 UA...