Option 93 - Set limit sensor set-point, “A” models only,
(option 90 set to 2)
This allows the thermostat limit sensor to be set,
typical application is fl oor htg. Press
+
until Option
93 is displayed, use
V
and
Λ
to select required
setting. If the temperature sensed by the limit
sensor exceeds the limit setting the output will be
turned off untill the temperature has dropped by
2°C “F10” will fl ash in the display.
Setting
Any value between 20 - 50°C (Factory setting is 27°C)
Option 94 - Confi gure digital input switch type, “A” models only,
(option 90 set to 3)
This allows switch type of digital input to be
confi gured. Press
+
until Option 94 is displayed, use
V
and
Λ
to select required setting.
Setting 0
Contacts NC, open circuit contact to force unit into
thermostat mode, short circuit contacts to return to normal
operation
Setting 1
Contacts NO, short circuit contacts to force unit into
thermostat mode, open circuit contacts to return to normal
operation (Factory setting)
Installa
tion Instruc
tions
GB
Summary of Contents for TP5001 series
Page 40: ...40 RF TP5001 TP5001 RF TP5001M 2 5 75 C 2 1 C 1 15 15 30 100 UA...
Page 41: ...41 TP5001 1 2 3 L N D E S1 S2 A M 230 1 5 2 DIL 1 2 UA...
Page 42: ...42 TP5001 TP5001 TP5001 TP5001A TP5001MA 1 2 3 TP5001 TP5001 RF RESET D E UA...
Page 45: ...45 RX3 1 1 3 5 2 1 2 PROG CH2 RX2 5 3 1 2 PROG CH3 RX3 5 TP5001 RF V TP5001 TP5001 UA...
Page 46: ...46 a V PROG 3 b V PROG 5 c V d RUN PROG UA...
Page 47: ...47 30 30 V 40 5 C 30 C 31 31 V 5 40 C 5 C 32 32 V 0 1 33 33 V 0 1 UA...
Page 48: ...48 34 34 V 0 3 3 6 6 9 9 12 12 35 34 3 6 9 12 PI 35 V 2 5 2 5 5 5 10 10 36 36 V 0 1 2 C 2 UA...
Page 49: ...49 38 38 V 0 1 37 36 1 2 37 V 0 1 1 2 2 3 3 4 4 40 2 4 6 40 V 1 2 4 6 UA...
Page 50: ...50 70 DIL 1 70 V 0 1 71 24 230 2 90 71 V 0 1 41 5 2 24 5 2 24 41 V 5 2 5 2 24 24 UA...
Page 52: ...52 90 A 90 V 0 1 2 93 3 94 93 A 90 2 93 V 2 C F10 20 50 C 27 C UA...
Page 53: ...53 94 A 90 3 94 V 0 1 UA...