Installation Guide
Termix VVX-I
6.2 DHW temperature control
DHW temperature control
There are various types of DHW temperature control used in
Danfoss substations.
DHW temperature should be adjusted to 45-50 °C, as this provides
optimal utilisation of DH water. At DHW temperatures above 55 °C,
the possibility of lime scale deposits increases significantly.
6.2.1 IHPT 180 controller (45–65 °)
IHPT is a self-acting flow-compensated temperature controller with
integrated differential pressure controller.
The IHPT operates at its best at DH supply temperatures of up to
100 °C.
By turning the handle for temperature setting in (+) direction
the setting is increased, by turning it in (-) direction the setting is
decreased.
Turns*
DHW Temperature Setting [°C]
0
64
1
61
2
58
3
55
4
52
5
48
6
44
7
43
*Start position: Handle turned fully in (+) direction.
The values are intended as a guide.
6.3 Other
6.3.1 Safety valve
The purpose of the safety valve is to protect the substation from
excessive pressure.
The blow-off pipe from the safety valve must not be closed. The
blow-off pipe outlet should be placed so that it discharges freely
and it is possible to observe any dripping from the safety valve.
It is recommended to check the operation of safety valves at
intervals of 6 months. This is done by turning the valve head in
direction indicated.
14
DEN-GT
VI.EH.G3.02 / LUK40440
Danfoss District Energy
Summary of Contents for Termix VVX-I
Page 20: ...Installation Guide Termix VVX I 20 DEN GT VI EH G3 02 LUK40440 Danfoss District Energy ...
Page 21: ...Installation Guide Termix VVX I Danfoss District Energy VI EH G3 02 LUK40440 DEN GT 21 ...
Page 22: ...Installation Guide Termix VVX I 22 DEN GT VI EH G3 02 LUK40440 Danfoss District Energy ...
Page 24: ...Installation Guide Termix VVX I Produced by Danfoss A S 03 2014 ...