Installation & User Guide

SonoSelect and SonoSafe

energy meters

Summary of Contents for SonoSafe 10

Page 1: ...1 03 2017 Danfoss VUIGB602 www heating danfoss com Installation User Guide SonoSelect and SonoSafe energy meters ...

Page 2: ...2 Danfoss Energy Meters 2017 03 VUIGB702 Installation User Guide SonoSelect and SonoSafe Note To ensure latest version of declaration please visit danfoss com ...

Page 3: ...low sensor installation 5 2 4 Mounting orientation calculator 5 2 5 Mounting of O ring and temperature sensor 6 2 6 Communication Expansion modules 7 2 7 Installation of module cable 10 2 8 Battery 11 3 Commissioning 12 3 1 Bleeding 12 3 2 Supply return configuration 12 3 3 Meter sealing 12 3 4 IP class 12 4 Function overview 13 4 1 Menu structure 13 4 2 Display explanation 14 4 3 Alarms 14 5 Devi...

Page 4: ...ned the meter will set alarm E13 in display Don t open unless for adding communica tion module replacing battery or installing cables Reset requires Bluetooth dongle 014U1963 and SonoApp service tool SonoSelect is delivered with the option of reconfiguring supply return using the Bluetooth dongle 014U1963 and SonoApp service tool Note Product is approved for ambient temperature between 5 55 C non ...

Page 5: ...nstallation Heat meters have red temp sensor in supply pipe and all cooling meters have blue temp sensor in supply pipe 2 3 Flow sensor installation Pipe position No limitations but avoid positions where air can be collected Rotation in pipe axis Flow sensor should be angled in 45 to 315 to avoid air collection in flow sensor 2 4 Mounting orientation calculator 4 x 90 Click 1a 2 3 1b ...

Page 6: ...ow sensor installation 1 Mount O ring on pin 2 Insert pin with O ring 3 Position O ring 4 Remove pin 5 Moist and insert sensor probe Tighten at torque 12 2 Nm To ensure accuracy and a tight seal the sensor installation should comply to EN1434 2 annex A Key Threaded connec tion size A Tapping bore size B G 18 5 mm G 24 mm G1 30 5 mm Note Tolerance on machined dimensions 0 5 mm Pipe fittings for use...

Page 7: ...f the display Wired M Bus is galvanically isolated from μC and pulse inputs The two pulse inputs can be programmed independently of each other see specification for pulse input module M Bus primary Lithium Thionyl Chloride battery half of AA size M Bus secondary M Bus supply Baud rate supported 300 2400 4800 9600 Communication protocol According to EN1434 3 EN13757 3 Battery life time 16 1 year fr...

Page 8: ...level input threshold 0 5 V Pull up resistor 100 kΩ Pulse length 100 ms Maximum frequency 5 Hz Pulse inputs According to EN1434 2 section 7 1 5 Classification of pulse input devices Class IB Battery life time 16 1 year Suitable for both electronic switch and Reed contact Data telegram Wired M bus Standard telegram Accumulated energy Accumulated volume Current flow Current power Supply temperature ...

Page 9: ...r orange 24 Meter bus blue or orange 25 Pulse input Pulse input 1 Brown 50 Pulse input 1 White 51 Pulse input 2 Brown 52 Pulse input 2 White 53 Cable specification Pulse input cables 10 m To ensure IP protection class connecting cable outer jackets must be Ø4 2 0 1 mm Communication cables delivered with heat meter Cable ends are stripped with crimped ferule 1 0 m ...

Page 10: ... to enclosure 4 Insert module follow ing guide on PCBA cover Insert cable through hole connect cable and fix to screw termi nals matching color and terminal numbers Fix cable s to cable relief Outer jacket no longer than 9 mm from cable relief line Press down 5 Close enclosure making sure that no cables inter fere with rubber sealing and other internal parts Click 6 Reset tamper alarm via Sono App...

Page 11: ...en en closure 3 Disconnect battery connector and remove battery 4 Short circuit battery connectors on PCB using a small flat head screwdriver 5 Connect new battery to PCB 6 Fit battery in enclosure 7 Close enclosure making sure that no cables interfere with rubber sealing or other internal parts 8 Confirm battery change by pressing the button 2 times within 120 seconds Reset tamper alarm E13 via S...

Page 12: ...es 4 For SonoSelect Run installation check using Bluetooth dongle 014U1963 and SonoApp service tool 3 2 Supply return configuration Only available for SonoSelect Use Bluetooth dongle 014U1963 and SonoApp service tool Configuration 3 3 Meter sealing Tamper monitor access level 1 Test seal verification mode Factory seal 3 4 IP class Calculator IP65 SonoSelect IP54 SonoSafe Flow sensor IP65 Temperatu...

Page 13: ...de SonoSelect and SonoSafe 4 Function overview 4 1 Menu structure Hours Alarm Energy Volume LOOP 1 Supply temp Display test All on Power Flow LOOP 2 Accounting date Monthly date 1 Monthly date 12 LOOP 3 Accumulated Current History log click click click Return temp ...

Page 14: ...eturn temperature Decimal emphasizer Temperature difference Units field 4 3 Alarms E01 System error E10 Transducer error E02 PCB error E11 Outside measured range E03 Battery empty less than 1 month E12 Negative flow E04 Battery low voltage E13 Tamper alarm E05 Battery low less than 12 months E14 High flow qss E06 Supply Temperature Error E15 Battery consumption too high E07 Return Temperature Erro...

Page 15: ...1 Module PCB 12 Bottom part PC 13 Temperature sensor 6 Disposal Item Material Disposal Battery AA cell Lithium thionyl chloride 620 mg Lithium Approved deposit for lithium batteries PCBA with display and com munication module Coppered epoxy laminate components soldered on PC TPE Electronic waste Cables Copper with PUR or PVC jackets Cable recovery Flow sensor including transducer and liner Brass s...

Page 16: ...s in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trad...