© Danfoss | DHS-SRMT/SI | 2019.10
4 | VU.SH.I1.02
User guide
Ultrasonic heat meter SonoMeter 30
Measurement units, flow pipe tagging,
calibration can be configured in “
Manufacturer
”
window.
Select energy units option in “
energy unit
” field
3.5 Volume calibration
and press “
set
” in order to configure what energy
units are used for measurements. If device is
successfully configured message “
Operation
done
” will pop up.
If device is going to be placed on flow pipe, tag
“
Flow pipe
”. If device is going to be placed on
return pipe, tag “
Return pipe
”. Press “
set
” to save
configuration into device. If device is successfully
3.5.1 Changing pipe type
configured message “
Operation done
” will pop
up. If is it needed that device measure only
heating energy, “
heating only
” box should be
tagged.
Press “
Read
” and then press “
Manufacturer Reset
”.
Disconnect the battery from the device. Use a
jumper to short the contacts on the device for
3.5.2 Resetting device
3 seconds in place where need to be connect
the battery. Connect a battery to the device and
reconfigure the date and time parameters.
Place jumper under removed device cover
(see Fig. 4). Press “
Read
” and then write error
“
Err %
” and flow “
Q
” data. Press “
set
” to save
3.5.3 Calibration
configuration into device. If device is successfully
configured message “
Operation done
” will pop
up.
Table 1
“Manufacturer” window parameters
No.
Name
Note
1
Calculator
-
2
Flow pipe (T1)
3
Return pipe (T2)
4
Heating only
Check this when device is only for heating energy measurements
5
Calibration
-
6
set
Press button to save configuration to device device
7
Calibration parameters
Write calibration parameters here
8
Energy unit
-
9
set
Press set to save energy unit parameter configuration
10
Manufacturer Reset
Press to reset the device
Fig. 4
Jumper Position “TEST”