© Danfoss | DCS (MWA) | 2017.02 

DKRCI.PI.IB0.A9.ML | 520H1621 | 2

DANSK

Installation

Kølemidler

Anvendelig til HCFC, HFC, R717 

(ammoniak) og R744 (CO

2

)

Brændbare kulbrinter anbefales ikke. 

Ventilen bør kun bruges i lukkede kredsløb. 

Kontakt venligst Danfoss, hvis du ønsker 

flere oplysninger.

Kompatibiliteten mellem medie, ventilhus 

og det respektive tætningsmateriale skal 

overholde Danfoss specifikation. I tvivl; 

brug Danfoss Coolselector eller kontakt 

Danfoss.

Temperaturområde

Driftsområde:

-50°C til + 100°C (-58°F til +212° F)
-50°C til -30°C (-58°F til -22°F) :

Fuld tæthed er kun garanteret, når trykket 

er mindre eller lig med 0,5 x P

set

.

Trykområde

SFV 20/25: 25 bar g (362 psi g). 

SFA 15/15-50: 40 bar g (580 psi g).

Danfoss Industrial Refrigeration A/S 

leverer sikkerhedsventiler, der er justeret 

til at kunne klare et vist tryk (angivet på 

ID-pladen) og forsejlet. Danfoss Industrial 

Refrigeration garanterer et korrekt tryk, så 

længe sejlet ikke er brudt.

Ventilen skal installeres med fjederhuset 

i oprejst position (fig. 1). Når sikkerheds-

ventilen installeres, er det vigtigt at undgå 

termisk og dynamisk tryk (vibrationer) (fig. 

2). Ventilens afgangsrør skal konstrueres 

således, at der ikke kan trænge snavs ind i 

ventilen (fig. 3).

Et U-rør fyldt med olie beskytter effektivt 

mod, at vand og snavs trænger ind, i 

tilfælde, hvor ventilernes afgangsrør fører 

ud til omgivelserne (fig. 4). 

Ventilen er konstrueret til at kunne modstå 

et højt indre tryk. Uanset hvilket system, 

der er tale om, skal det være konstrueret 

til at undgå væskefælder og reducere 

risikoen for hydraulisk tryk forårsaget af 

termisk ekspansion. Sørg for, at ventilen 

er beskyttet mod kortvarige tryk såsom 

“væskeslag” i systemet. 

Svejsning

Hvis svejsefittings anvendes, bør disse 

afmonteres, mens der svejses (fig. 5). 

Kun materialer og svejsemetoder, der er 

kompatible med flangens materialer, kan 

bruges til svejsning på flangen. 

Undgå svejserester og snavs i husets og 

rørenes gevind.

Montering

Fjern svejserester og snavs fra rør og huset, 

før ventilerne monteres. Monter ventilerne 

som vist i fig. 6.

Efter installation og under drift, må 

eventuelle tilsluttede rør kun tilsluttes 

uden kraft og moment.

Farver og identifikation

Ventilerne er belagt med zink-krom fra 

fabrikkens side. Hvis der er behov for 

yderligere rustbeskyttelse, kan ventilerne 

males. 

Nøjagtig identificering af ventilen udføres 

ved hjælp af ID-pladen på ventilhuset.

Kontakt Danfoss i tilfælde af tvivl. 

Danfoss påtager sig intet ansvar for fejl eller mangler. 

Danfoss Industrial Refrigeration forbeholder sig ret til at 

ændre produkter og specifikationer uden forudgående 

varsel.

ENGLISH

Installation

Refrigerants

Applicable to HCFC, HFC, R717 (Ammonia) 

and R744 (CO

2

).

Flammable hydrocarbons are not 

recommended. The valve is only 

recommended for use in closed circuits. For 

further information please contact Danfoss.

The compatibility between medium, 

housing and respective sealing material 

must comply with Danfoss specification. In 

doubt; use Danfoss Coolselector or contact 

Danfoss.

Temperature range

Operation range:

–50°C to +100°C (-58°F to +212°F)  
–50°C to -30°C (-58°F to -22°F):  

Full tightness only guaranteed when the 

pressure is less or equal to 0.5 x P

set

.

Pressure range

SFV 20/25: 25 bar g (362 psi g). 

SFA 15/15-50: 40 bar g (580 psi g).

Danfoss Industrial Refrigeration A/S is 

supplying safety valves adjusted for a 

certain pressure (indicated on the ID-plate) 

and sealed. Danfoss Industrial Refrigeration 

guarantees correct pressure as long as the 

seal remains unbroken.

The valve should be installed with the 

spring housing upwards (fig. 1). By 

mounting of the safety valve it is important 

to avoid the influence of thermic and 

dynamic stress (vibrations) (fig. 2). The 

outlet pipe of the valve must be designed 

as to prevent dirt from penetrating into the 

valve (fig. 3).

For valves with outlet in the open air, an 

oil filled U-pipe is an effecient protection 

against the entrance of water and dirt (fig. 4).

The valve is designed to withstand a high 

internal pressure. However, the piping 

system should be designed to avoid liquid 

traps and reduce the risk of hydraulic 

pressure caused by thermal expansion. It 

must be ensured that the valve is protected 

from pressure transients like “liquid 

hammer” in the system.       

Welding

If welding fittings are applied, these 

should be dismounted during the welding 

process (fig. 5). Only materials and welding 

methods, compatible with the flange 

material, must be welded to the flange. 

Avoid welding debris and dirt in the 

threads of the housing and pipes.

Assembly

Remove welding slag and dirt from tubes 

and housing before the valve is mounted. 

Mount the valve as shown in fig. 6.

After installation and when operating, any 

connected pipes must only be connected 

force and torque free.

Colours and identification

The valves are Zinc-Chromated in the 

factory. If further corrosion protection 

is required, it can be painted. Precise 

identification of the valve is made via the 

ID-plate on the valve housing.

In cases of doubt, please contact Danfoss. 

Danfoss accepts no responsibility for errors and 

omissions. Danfoss Industrial Refrigeration reserves the 

right to make changes to products and specifications 

without prior notice.