Technical data

Maximum Working Pressure:

Type

RT 113E RT 112E RT 1AE RT 116E RT 5E

RT 6AEW

RT 6AEB
RT 6AES

RT 117E RT 121E RT 260AE RT 262AE

MWP 
[bar]

0.4

7

22

22

22

34

 1

)

42

7

22

11

1

)

 

28 bar P

e

 when used as safety equipment acc. to EN12263

Permissible ambient temperature: 

-20 – 65 °C

Intrinsically safe specification:

Ui  = 29 V                   Ci  = 0.5 nF
li   = 0.5 A                  Li  = 0.2 µH
Pi  = 1 W

Contact load:

max. 100 mA, 30 V AC / DC

min. 1 mA, 5 V AC / DC

Must be used with a certified Ex ia barrier 
satisfying the input parameters.

Installation 

A set of Pg13.5 cable gland is attached to the RT in a separate bag. To
ensure IP66 (units with automatic reset) or IP54 (units with external
reset) grade of RT enclosure it is necessary to assemble this gland
as shown in the fig. 6. If this gland is not used with a cable, a metal
blinding should be also assembled.
The RT pressure switch is designed for fitting on the valve panel or the 
compressor. Use the mounting holes (25).  If the unit can be exposend 
to vibration, it should be mounted on a resilient pad. If pressure 
pulsations occur in the system at the point where the pressure switch 
is connected, these should be effectively damped, as for example, by 
connecting the RT unit to the system via damping coil.

Electrical connection

 

(see fig. 8 and fig. 9)

START = make. STOP = break. DIFF = differential.
Cable diameter: 6 – 14 mm
The earth terminal (38) should be connected to earth.
Wire dimension: min. 0,75 mm²

Adjustment

RT 1AE, RT 116E, RT 5E, RT 117E, RT 112E, RT 113E, RT 121E 
(see fig. 1, fig. 2 and fig. 8)

Set the pressure switch for minimum actuating pressure (range setting). 
Setting is done by rotating the knob (5), at the same time reading the 
main scale (9).
The differential is set by rotating the differential adjusting nut (19) 
according to the nomogram concerned (fig. 5 or fig 7).
Maximum actuating pressure is the sum of the pressure setting and the 
differential.

RT 260AE, RT 262AE 
See fig. 4 and fig. 8

Set the required differential pressure with the setting disc (5) while at 
the same time reading the scale (9).

RT 6AEW, RT 6AEB, RT 6AES (see fig. 3 and fig. 9)

After removing the seal cap (7), set the cut out pressure with the 
uncovered range spindle while reading the scale (9).

 

 

Safety requirements

 

1. 

   The refrigeration system must always comply with European 

Ex installation standard, EN 60079-14, any local directive and 
legislation as well as any other regulation applying in the area of 
installation.

 
 2.

   RT-E switch must be used only with reliable means of limiting 

the voltage and current to prevent sparks between the contact 
surfaces. The equipment to be used for electrical load limiting 
must always be approved for use in the zone concerned.

 3.

   Cable and cable entries approved for the application must be used. 

Cables must not be in contact with sharp edges. The cable must 
be connected with adequate stress relief in order to prevent that 
pulling forces can be carried through the cable to the terminal.

 4.

   In the event of pressure pulsations in the system, where the switch 

is connected, these must be effectively damped to prevent fatigue 
failure on the bellows. The cycle frequency of the RT-E switch must 
be kept as low as possible. The vibration level must be kept as low 
as possible.

 5.

   It is recommended to regularly check the function of the RT-E 

switch.

 6.

   Only apparatus designed, constructed and released by Danfoss 

must be used for application concerned. Danfoss can accept no 
responsibility in case of alterations made on the pressure switches 
or the use of them against the instructions of Danfoss.

 7.

   Any overload of the RT switch must be prevented. Overloaded or 

damaged apparatus must be exchanged.

 8.

   Only authorised persons, who are certified in installing and 

maintaining refrigration system may do the installation, 
maintenance and exchange of the switch.

 9.

  Use only appropriate tools.

 10.

  Dispose of the switch in an environmentally-friendly way.

 11.

   RTE switches must be installed in area where is low risk of 

mechanical damage.

 12.

   Components within the equipment can exceed  the enclosure 

temperature by 1K (1°C). When the media temperature exceeds 
80°C, it is the responsibility of the user to ensure that the media 
temperature does not cause a thermal ignition risk on parts 
between the media and the switch enclosure. Maximum media 
temperature on pressure switch is 100°C.

 13.

   Isolation of the intrinsically safe circuit to ground and to the 

contact mounting screw has been verified through 500VACrms 
dielectric strength testing, carried out in accordance with IEC 
60079-11:2011 section 10.3.

 14.

   Surface of the front cover is sputtered with stainless steel - avoid 

abrasion.

15.

    Power must be switched off before maintenance and opening the 

   RT-E.

Specific conditions of use:

The enclosure fascia has been coated with a layer of stainless steel to prevent the 
accumulation of electrostatic charge. In order to ensure that there is no accumulation of 
electrostatic charge on the enclosure, the end user shall ensure that the external metal 
work of the enclosure is locally bonded to earth. Information on the durability of the 
coating with regards to use of the equipment is contained within the instruction manual.

Temperature class

Process temperature limit [°C]

T4 – T1

T5
T6

100

94
79

Product marking: RT 6AEW, RT 6AEB, RT 6AES

 
 
 

Ex ia IIC T6...T1 Gb    -20 °C ≤ Ta ≤ 65 °C

DEMKO 14 ATEX 1406X, Rev. 3 

IECEx ULD 14.0013X

U

i

 = 29 V    I

i

 = 0.5 A    P

i

 = 1 W

C

i

 = 0.5 nF    L

i

 = 0.2 μH

II2G

Product marking: RT112E, RT113E, RT1AE, RT116E, 
RT5E, RT117E, RT260AE, RT262AE, RT9E, RT14E, 
RT101E, RT107E, RT121E, RT123E

                                 

            

Ex ia IIC T6...T1 Gb    -20 °C ≤ Ta ≤ 65 °C