ENGLISH

Technical data
Fail Safe Pressure limiter type RT 110

Stainless Steel as a limiting device of 

the boiler - according to EN12953-9.

Electrical fitting: 

The RT 110 contact system is designed

according to EN12953-9 requirements

included 250000 switching cycles with

electrical parameters marked on the RT 110

contact system plastic cover.

Using the appliance other than described

AC-1, AC-3, AC-15 or DC-13 modes, may not

be as a limiter.

The RT contact system and any cooperated

external contactors or relays shall, against

the effects of short circuits, be over current 

protected with 0,6 safety factor. It means, 

that the nominal current of the device, as 

stated by the manufacturer, is to be multi-

plied by a safety factor of 0.6.

Example:

Rated load for AC15 is 1A.

Safety factor is 0,6 in consequence, 

fuse = 1A x 0,6 = 0,6A or less.

Endurance of any external contactors and

relays must be according to EN12953-9,

which means 250000 switching cycles

under conditions similar to operating 

conditions and be capable of a mechani-

cal life time of 3000000 switching cycles. 

Conditions similar to operating conditions 

covers chemical and climatic influences as 

well as electrical and mechanical stresses. 

In addition, contactors must fulfil EN60947 

and relays must fulfil EN60255.

Wires for connecting the RT 110 must be

according to the specifications of 

prEN 50156-1 standard and may not de-

crease electrical safety or IP-protection of 

the appliance. After connection to the wir-

ing use cable ties or similar to protect the 

wires of slippingout of the screw-terminals 

in order to prevent unintended movement 

of the wires.

Generally, when there is no pressure 

working on the appliance:

 

– Terminal 1 is C (common one)

 

– Terminal 2 is NC (terminal 2 is normally 

  connected to common terminal 1)

 

– Terminal 4 is NO (terminal 4 is normally 

  opened with common terminal 1) 

 

 

 

NOTICE

, there are two different ways of

working for pressure limiter: one as a

pressure limiter for rising and another one 

as a pressure limiter for falling.

For identification, there is adequate

description on the bottom of housing (see 

below examples).

For rising:

When the pressure rise up and achieve set-

ting point, contacts change:

 

– 1-2 disconnection

 

– 1-4 connection

When the pressure fall down below setting 

point + diff erential value, contacts change 

back:

 

– 1-2 connection

 

– 1-4 disconnection

For rising:

 

When the pressure fall down and achieve

setting point, contacts change:

 

– 1-2 connection

 

– 1-4 disconnection

When the pressure rise up above setting

point + diff erential value, contacts change

back:

 

– 1-2 disconnection

 

– 1-4 connection

Locking/reset mechanism:

Since the pressure limiter type RT 110 has 

no lockout with manual resetting, this 

functions must be realized externally as 

a part of a safety logic e.g. by external 

contactors and/ or relays which then are to 

be used according to the requirements of 

prEN50156-1 standard for safety relevant 

hardware. External closure must not be 

interlocked, while loss of auxiliary energy 

must lead to a closure.

Resetting must not be automated, it has to

be performed manually. Resetting on fault

must lead to a repeated closure.

When RT limits, for rising or falling applica-

tion, the external safety logic must change 

to the fail safe position. 

 

Pressure fitting:

In order to prevent malfunction of the 

limiter, the pressure installation must be 

according to Danfoss Instruction 017R9315 

and below description harmonized with 

the requirements of EN12953-9. 

For safety purpose, accessory 060-333366 

and 060-007166 can not be used with the 

limiter!

Steam boilers:

Connecting pipes for the limiter shall be

connected to the steam space of the boiler

and if necessary, the limiter shall be

protected from the steam temperature by

a water seal. If an insolating valve is fitted

on the connection pipe, an insulation valve

shall be installed which shall be capable of

being locked.

Fully fl ooded hot water generators:

The limiter shall be connected to the supply

pipe before the fi rst shut-off valve.

The limiter body shall be installed verti-

cally so that dirt does not enter the limiter. 

If there is the possibility of sludge build-up 

in the connection pipe it shall be possible 

to purge the pipe. Such purging must 

not remove the water seal or introduce 

dirt into the water seal. In addition, the 

connection pipe and its boiler connection 

must be designed for cleaning and inspec-

tion and have a clear bore of at least:

1. where pipe supplies only the imiter: 

  ø8mm- if pipe is less than 1m long. 

 ø15mm - if pipe is greater than 1m long.

2. where pipe supplies the limiter in 

  addition to other limiters: 

  ø20mm - for all lengths of pipes.

Provision shall be made for functional test-

ing of the limiter. The result of the test shall 

be clearly indicated to the boiler operator.

Setting:

RT 110 with factory setting:

RT 110 with factory setting are secured by

manufacturers sealing. Setting screw and

plastic cover with window can not be turn-

ed or removed without breaking the seal.

Connection of wires to the RT 110 contact

system must be performed after removing 

the sealing and plastic cover, without any 

changing of the setting value. In order to 

protect RT device against changing chang-

ing of the setting, after wiring, a seal must 

be applied by the customer.

RT 110 without factory setting:

The same conditions as in the RT 110 with 

factory setting paragraph. Checking 

accuracy of the setting by the customer 

must be done with calibrated pressure 

gauge. Scale can be used only as an indica-

tion of the pressure setting. 

Adjusting the appliance to more than 3 

bar or less than 0.05 bar will cause faulty 

operation to the appliance and safe 

function is not reliable any more!

Summary of Contents for RT 110

Page 1: ...with manual resetting this functions must be realized externally as a part of a safety logic e g by external contactors and or relays which then are to be used according to the requirements of prEN50156 1 standard for safety relevant hardware External closure must not be interlocked while loss of auxiliary energy must lead to a closure Resetting must not be automated it has to be performed manuall...

Page 2: ...dkoblingsspærring med man reset skal disse funktioner klares eksternt som en del af det logiske sikkeredssystem fx gennem eksterne kontaktorer og eller relæer som så skal anvendes på sikker hedsrelevant udstyr i henhold til kravene i EN50156 1 Ekstern afspærring må ikke kunne blokeres og tab af hjælpeenergi skal føre til afspær ring Reset må ikke i en fejlsituation skal igen føre til afspærring Nå...

Page 3: ...en Anforderungen der prEN50156 1 für sicherheitsrelevante Schutzeinrichtungen und Bauteile einzusetzen sind Die externe Verriegelung darf nicht blokki erbar sein und ein Verlust der Hilfsenergie muss zur Verriegelung führen Die Rück setzung darf nicht automatisiert werden sondern darf nur von Hand ausführbar sein Rücksetzen im Fehlerfall muß zur erneuten Verriegelung führen Wenn der RT begrenzend ...

Page 4: ...onction doit être exécutée extérieurement et donc faire partie d un dispositif logique de sécurité par exemple via des contacteurs ou des relais externes qui doivent alors également être utilisés conformément à la norme prEN50156 1 s appliquant aux matériels de sûreté La fermeture externe ne doit pas être enclen chée alors que la perte d énergie auxiliaire doit mener à une fermeture Le réarmement ...