Danfoss Redan PM Instruction Manual Download Page 1

11

Danfoss District Energy 

VI.IQ.E1.51 

DKDHR

Instruction Manual 

 

901.000.S 

 

 

                                                         Code No. 004B6112

PM controller
PM-Regler
PM-regulator

English - GB 

The Danfoss Redan PM domestic hot water controller is used for controlling the domestic hot water temperature in combination with a 

plate heat exchanger.

The controller is pressure-controlled, ensuring that district heating water is led to the instantaneous water heater only when hot water is being

tapped. Due to the construction of the controller proportionality exists between the district heating water flow and the domestic hot water

consumption. By this a constant domestic hot water temperature is guaranteed for big and small tap loads.

Installation

The controller must be installed in a way that allows the medium to flow in the direction indicated by the arrows. The insertion position is

optional, as the PM controller is pressurecontrolled and is not based on an air or liquid filling. The PM controller is typically installed in

the district heating return of the water heater.

German - DE 

Der Danfoss Redan PM-Regler wird für die Regelung der Brauchwarmwassertemperatur in Verbindung mit einem Plattenwärmetauscher 

verwendet.

Der Regler arbeitet druckgesteuert, das heisst, daß erst bei Warmwasserzapfung ein Durchfluss sowohl primär (Fernwärme) als auch 

sekundär (Warmwasser) durch den Wärmetauscher ermöglicht wird. Es besteht ein Proportionalverhalten zwischen Fernwärmedurchfluss

und der Warmwasserentnahme. Dadurch gibt es keine Temperaturunterschiede bei kleinen oder grösseren Zapfmengen.

Einbau

Der Regler muss so montiert werden, daß der Volumenstrom in Pfeilerichtung verläuft. Die Einbaulage ist beliebig, da der Regler druckges-

teuert arbeitet, und nicht auf eine Luft- oder Wasserfüllung basiert. Üblicherweise wird der PM-Regler wegen der niedrigeren Temperaturen

im Fernwärmerücklauf montiert. 

Danish - DK 

Danfoss Redan PM-regulator anvendes til styring af varmtvandstemperatur i forbindelse med en pladevarmeveksler eller eventuelt en 

rørveksler / spiralvandvarmer.

Regulatoren er trykstyret, således at der alene åbnes for fjernvarmevand til vandvarmeren, når der tappes varmt vand. Regulatoren er 

konstrueret, så der er proportionalitet mellem varmtvandsmængden og mængden af fjernvarmevand, der ledes gennem regulatoren.

Derved opnås ens temperatur for store og små tapninger.

Montering

Regulatoren monteres, således at gennemstrømning sker i de indstøbte piles retning. Regulatoren kan orienteres valgfrit, idet den er

trykstyret og ikke er baseret på en luft- /eller væskefyldning. PM-regulatoren placeres typisk på vandvarmerens fjernvarme returside.

Summary of Contents for Redan PM

Page 1: ... druckgesteuert das heisst daß erst bei Warmwasserzapfung ein Durchfluss sowohl primär Fernwärme als auch sekundär Warmwasser durch den Wärmetauscher ermöglicht wird Es besteht ein Proportionalverhalten zwischen Fernwärmedurchfluss und der Warmwasserentnahme Dadurch gibt es keine Temperaturunterschiede bei kleinen oder grösseren Zapfmengen Einbau Der Regler muss so montiert werden daß derVolumenst...

Page 2: ... temperature lower than DHW from unit Defective non return valve in hot water circulation circulation return pipe is getting cold during tapping of hot water Lime scale precipitation in plate heat exchanger for DHW t primary too low during DHW tapping Dirt in PM controller DCW flow too high big nominal diameter of pipe high DCW pressure in total maximum 16 17 litre per minute See back of the page ...

Page 3: ...HW Cost free repairs Danfoss agrees to repair or replace at the discretion of Danfoss such Products that on Danfoss examination are found to be defective at the time of delivery due to faulty manufacture design and or defective materials provided Customer makes a claim to Danfoss within 12 months from the date of delivery however not exceeding 18 months from the date stamped on the product If defe...

Page 4: ...defekt WW Zapftemperatur niedriger als WW Zuleitung Rückschlagventil in WW Zirkulation defekt Zirkulationsrohr wird kalt bei WW Zapfung Wärmeübertrager für WW verkalkt t primär zu niedrig während WW Zapfung Verschmutzung des PM Reglers Zu große KW Durchflußmenge große Rohrnennweiten hohe KW Druck insgesamt max 16 17 Liter pro Minute Siehe andere Seite Sieb reinigen Rückschlagventil reinigen oder a...

Page 5: ...der Zapfstelle kontrollieren Empfohlene Zapftemperatur 45 48 C nie höher als 50 C um Kalkbildung im WW Bereiter zu vermeiden Sachmängelgewährleistung Danfoss verpflichtet sich innerhalb der gewährleistungsfristen die von ihr hergestellten und gelieferten Produkte nachzubessern oder auszutauschen wenn sie sich nach Überprüfung bei Danfoss als defekt erwiesen haben Alle Ansprüche des Käufers gleich ...

Page 6: ...et Kontraventil på cirkulationsstreng defekt cirkulationsrør bliver koldt under varmtvandstapning Kontraventil på fjernvarme retur på vandvarmer defekt Vandvarmeren tilkalket dårlig afkøling under tapning Snavs i PM regulator Se bagside Rens snavssamler Rens eller skift kontraventil Rens eller skift kontraventil Rens eller skift kontraventil Afhjælpes ved udsyring Rens regulatoren Se bag side For ...

Page 7: ...les ved at dreje håndtaget mod rød varmere eller blå koldere Temperaturen indstilles under varmtvandstapning 8 10 liter pr minut til 45 48 C Temperaturen bør aldrig overstige 50 C for at undgå kalk udfældning i vandvarmeren Vederlagsfri reparation Danfoss Redan A S forpligter sig til efter eget valg at repare re eller omlevere produkter som efter Danfoss Redan s undersøgelse viser sig at være mang...

Page 8: ...Produced by Danfoss Redan A S 12 2010 Produced by Danfoss Redan A S 08 2013 ...