FRCC.PC.017.A1.02

20

A

PPLICATION

 

GUIDELINES

S

OUND

 

AND

 

VIBRATION

 

MANAGEMENT

Running sound level

Sound generation in a 
refrigeration system / air 
conditioning system

Compressor sound 
radiation

Performer® Heat Pump scroll compressors 
are designed with optimised discharge ports 

and wrap geometry to reduce the sound level 
when a compressor is running. 

Typical sound and vibration in refrigeration and 
air conditioning systems encountered by design 
and service engineers may be broken down into 
the following three source categories.

Sound radiation:

 This generally takes an air-

borne path.

Mechanical vibrations:

 These generally extend 

along the parts of the unit and structure.

Gas pulsation:

 This tends to travel through the 

cooling medium, i.e. the refrigerant.

The following sections will focus on the causes 
and methods of mitigation for each of the above 
sources.

For sound radiating from the compressor, the 
emission path is airborne and the sound waves 
are travelling directly from the machine in all 
directions.

The  Performer®  Heat  Pump  scroll  compressor  is 
designed to be quiet and the frequency of the 
sound generated is pushed into the higher rang-
es, which not only are easier to reduce but also 
do not generate the penetrating power of lower-
frequency sound.

Use of sound-insulation materials on the inside 
of  unit  panels  is  an  eff ective means of substan-
tially reducing the sound being transmitted to 
the outside. Ensure that no components capable 
of transmitting sound/vibration within the unit 
come into direct contact with any non-insulated 
parts on the walls of the unit.

Because of the Danfoss’s unique design of a full-
suction gas & oil cooled motor, compressor body 
insulation across its entire operating range is 
possible. 

Model

Code 4

Code 5

Sound power (dBA)

Without jacket

Sound power (dBA)

With jacket

Sound power (dBA)

Without jacket

Sound power (dBA)

With jacket

HHP015

70

62

70

62

HHP019

70

62

70

62

HHP021

71

63

71

63

HHP026

71

63

71

63

HHP030

72

64

72

64

HHP038

72

64

72

64

HHP045

73

65

-

-

Mechanical vibrations

Vibration isolation constitutes the primary meth-
od for controlling structural vibration. Performer® 
Heat Pump scroll compressors are designed to 
produce minimal vibration during operations. The 
use of rubber isolators on the compressor base 
plate or on the frame of a manifolded unit is very 
eff ective in reducing vibration being transmitted 
from the compressor(s) to the unit. Rubber grom-
mets are supplied with all Danfoss compressors. 
Once  the  supplied  rubber  grommets  have  been 
properly mounted, vibration transmitted from 
the compressor base plate to the unit are held to 

a strict minimum. In addition, it is extremely im-
portant that the frame supporting the mounted 
compressor be of suffi

  cient mass and stiff ness to 

help dampen any residual vibration potentially 
transmitted to the frame. The tubing should be 
designed  so  as  to  both  reduce  the  transmission 
of vibrations to other structures and withstand 
vibration without incurring any damage. Tubing 
should  also  be  designed  for  three-dimensional 
fl exibility. For more information on piping design, 
please see the section entitled "Essential piping 
design considerations".

Gas pulsation

The  Performer®  Heat  Pump  scroll  compressors 
have  been  designed  and  tested  to  ensure  that 
gas pulsation has been optimised for the most 
commonly encountered pressure ratio. On heat 
pump installations and other installations where 
the pressure ratio lies beyond the typical range, 
testing should be conducted under all expected 

conditions and operating confi gurations to en-
sure that minimum gas pulsation is present. If an 
unacceptable level is identifi ed, a discharge muf-
fl er with the appropriate resonant volume and 
mass should be installed. This information can be 
obtained from the component manufacturer.

Summary of Contents for Performer HHP015T4

Page 1: ...Performer Heat Pump scroll compressors 50 Hz R407C Selection application guidelines MAKING MODERN LIVING POSSIBLE ...

Page 2: ......

Page 3: ......

Page 4: ...imum Continuous Current 10 Max Oper A Maximum Operating Amp 10 Winding resistance 10 Electrical connections 10 Nominal capacitor value 11 Internal motor protection 11 Phase sequence and reverse rotation protection 11 Voltage imbalance 11 APPROVALS AND CERTIFICATIONS 12 Approvals and certificates 12 Pressure equipment directive 97 23 EC 12 Low voltage directive 73 23 EC 93 68 EC 12 Internal free vol...

Page 5: ... system 20 Compressor sound radiation 20 Mechanical vibrations 20 Gas pulsation 20 INSTALLATION 21 System cleanliness 21 Compressor handling and storage 21 Compressor mounting 21 Compressor holding charge 21 Tube brazing procedure 21 Brazing material 21 Vacuum evacuation and moisture removal 22 Liquid line filter driers 23 Refrigerant charging 23 Insulation resistance and dielectric strength 23 Com...

Page 6: ...he motor stator is rigidly attached to the shell The rotor is shrink fit onto the eccentric shaft The shaft is supported by two bearings one in the crankcase and the second below the motor SCROLL COMPRESSION PRINCIPLE Scroll compressor components ...

Page 7: ...is illustrat ed below The centre of the orbiting scroll traces a circular path around the centre of the fixed scroll This movement creates compression pockets be tween the two scroll elements Low pressure suction gas is trapped within each crescent shaped pocket as it forms continuous motion of the orbiting scroll serves to seal the pocket which decreases in volume as the pocket moves towards the c...

Page 8: ...plication H high temperature Family HP heat pump R407C PVE Nominal capacity Model variation T motor design Motor voltage code 4 380 400V 3 50 Hz 5 220 240V 1 50 Hz Motor protection L internal motor protection Tubing and electrical connections P brazed connections spade terminals C brazed connections screw terminals Other features Oil sight glass Oil equali sation Oil drain LP gauge port Gas equali...

Page 9: ...810 1 7 9 270 1 7 10 900 1 7 12 690 1 7 50 3 180 1 7 3 680 1 7 4 340 1 8 5 180 1 9 6 180 1 9 7 340 2 0 8 670 2 1 10 160 2 2 11 830 2 2 60 4 660 2 3 5 300 2 4 6 110 2 4 7 070 2 5 8 200 2 6 9 480 2 7 10 930 2 8 HHP021T4 40 3 530 1 4 4 250 1 5 5 090 1 6 6 080 1 7 7 230 1 7 8 570 1 8 10 100 1 8 11 840 1 7 13 820 1 7 50 3 430 1 6 4 080 1 8 4 860 1 9 5 770 2 0 6 830 2 1 8 070 2 1 9 500 2 2 11 140 2 2 13...

Page 10: ... spade terminals P terminal box type 1 7 41 Ø 41 29 5 5 16 18 UNC self tapping Recommended torque for mounting bolts 11 Nm 1 Nm Ø11 238 8 4 x Ø 19 0 20 0 95 25 128 5 111 3 69 4 71 4 34 31 45 14 109 7 95 25 190 25 190 50 238 8 190 25 190 75 HHP 015 019 021 026 394 4 Suction line 1 19 13 19 23 3 4 inch 163 5 165 5 72 1 75 1 360 4 194 9 230 8 10 7 19 Discharge line 12 75 12 85 1 2 inch P6 All dimensi...

Page 11: ...9 5 5 16 18 UNC self tapping Recommended torque for mounting bolts 11 Nm 1 Nm Ø11 Ring connect screw terminals C terminal box type C T S T R T 239 190 25 190 75 95 25 133 6 121 78 5 80 5 182 54 184 54 Suction line 22 30 22 48 7 8 inch Discharge line 12 75 12 85 1 2 inch 92 0 94 0 402 7 202 4 261 19 10 9 435 9 34 31 45 14 4 x Ø 19 0 20 0 239 190 25 190 75 119 2 95 25 HHP030 038 045 All dimensions i...

Page 12: ...abelled T1 T2 and T3 For single phase applications the terminals are labelled C common S start and R run Prior to energizing verify that leads and terminal connectors are in proper working condition Warning For safety reasons make voltage meas urements at the unit contactor not at compressor terminals Always keep the terminal cover in place when the compressor is energized The terminal cover and g...

Page 13: ...r Amp Winding resistance Winding resistance is the resistance between indicated terminal pins at 25 C resistance value 7 Winding resistance is generally low and it requires adapted tools for precise measurement Use a dig ital ohm meter a 4 wires method and measure under stabilised ambient temperature Winding resistance varies strongly with winding tempera ture If the compressor is stabilised at a ...

Page 14: ...the average for all phases Phase sequence and reverse rotation protection Voltage imbalance Internal motor protection The Performer Heat Pump scroll compressors are equipped with an internal line break protector mounted on the motor windings The protector is an automatic reset device containing a snap ac tion bimetal switch Internal protectors respond to over current and overheating They are desig...

Page 15: ...e directive 73 23 EC 93 68 EC Internal free volume CE 0062 or CE 0038 European Directive All models UL Underwriters Laboratories All models Other approvals certificates CB certificate available upon request Products Manufacturer s declaration of incorporation ref EC Machines Directives 98 392 CE Contact Danfoss Products Internal free volume at LP side without oil litre HHP015 019 021 026 2 93 HHP030...

Page 16: ...cant provides the best possible result in terms of reliability and compres sor lifetime The PVE lubricant is compatible with R22 which makes the Performer Heat Pump scroll compres sors a very versatile multi refrigerant solution Motor supply The Performer Heat Pump scroll compressors can be operated at nominal voltages as indicated in section Electrical data connections and wir ing Under voltage a...

Page 17: ...rmostat Continuous opera tions beyond the compressor s operating range will cause serious damage to the compressor A DGT accessory is available from Danfoss refer to section Spare parts and accessories The operating envelope for Performer Heat Pump scroll compressors are given in the figure below where the condensing and evaporating temperatures represent the range for steady state operation Under ...

Page 18: ... in duce such a problem The minimum low pressure safety switch loss of charge safety switch setting is given in the above table For systems without pump down the LP safety switch must either be a manual lockout device or an automatic switch wired into an electrical lockout circuit The LP switch tolerance must not allow for vacuum op erations of the compressor LP switch settings for pump down cycle...

Page 19: ...k to the compressor when stopped see fig 2 The maximum elevation difference between the in door and outdoor section cannot exceed 8 m System manufacturers should specify precau tions for any applications that exceed these limits to ensure compressor reliability Piping should be designed with adequate three dimensional flexibility It should not be in contact with the surrounding structure unless a pro...

Page 20: ...itions As such reversible cycle applications require spe cific precautions for ensuring a long compressor life and satisfactory operating characteristics Regardless of the refrigerant charge in the system specific tests for repetitive flood back are required to confirm whether or not a suction accumulator needs to be installed A crankcase heater and dis charge gas thermostat are required for reversibl...

Page 21: ...n device OUTDOOR COIL Expansion device SYSTEM CHARGE TEST REQUIRED ACCEPTABLE SUMP SUPERHEAT TEMPERATURE ACCUMULATOR REQUIRED SYSTEM CHARGE TEST REQUIRED ACCEPTABLE SUMP SUPERHEAT TEMPERATURE ACCUMULATOR REQUIRED 3 6 kg 1 5 4 kg 2 3 6 kg 1 5 4 kg 2 3 6 kg 1 5 4 kg 2 3 6 kg 1 5 4 kg 2 3 6 kg 1 5 4 kg 2 INDOOR COIL Expansion device OUTDOOR COIL Expansion device 0 2 4 6 8 10 12 14 16 18 25 20 15 10 5...

Page 22: ...pped with an internal pressure relief valve for protec tion against blocked condenser and fan failure conditions High pressure ratio Danfoss recommends the use of a thermostatic expansion valve for all air conditioning and heat pump applications A TXV has two key benefits it provides modulating control of the system under varying load conditions and it protects the com pressors from flood back durin...

Page 23: ...jacket Sound power dBA With jacket Sound power dBA Without jacket Sound power dBA With jacket HHP015 70 62 70 62 HHP019 70 62 70 62 HHP021 71 63 71 63 HHP026 71 63 71 63 HHP030 72 64 72 64 HHP038 72 64 72 64 HHP045 73 65 Mechanical vibrations Vibration isolation constitutes the primary meth od for controlling structural vibration Performer Heat Pump scroll compressors are designed to produceminima...

Page 24: ...densablesubstancesand system contaminants such as metal shavings sol der and flux have a negative impact on compres sor service life Many of these contaminants are small enough to pass through a mesh screen and can cause considerable damage within a bearing assembly The use of highly hygroscopic POE and PVE oils in R407C and R410A compressors requires that the oil be exposed to the atmosphere just ...

Page 25: ...n cause substantial damage to the internal parts of the system and compressor The PVE oil used in Performer Heat Pump scroll compressors is highly hygroscopic and will rap idly absorb moisture from the air The compres sor must therefore not be left open to the atmos phere for a long period of time The compressor fitting plugs shall be removed just before brazing the compressor Before eventual unbra...

Page 26: ...he Danfoss DCL solid core filter driers containing activated alumina are recommended The drier is to be oversized rather than under sized When se lecting a drier always take into account its capac ity water content capacity the system refrigera tion capacity and the system refrigerant charge Insulation resistance and dielectric strength Insulation resistance must be greater than 1 meg ohm when meas...

Page 27: ...ll together on one pallet They can be ordered in quantities of full pallets only multiples of 12 Each industrial pack pallet contains following accessories 4 grommets per compressor 4 sleeves per compressor Packaging Single pack Packaging details Ordering information and packaging Model Weight for single pack kg Weight for Industrial pack kg HHP015 019 021 026 198 390 HHP030 038 045 249 492 Model ...

Page 28: ...uction Multipack 10 120Z0365 Rotolock adaptor 1 1 2 HHP all discharge Multipack 10 Type Code n Description Application Packaging Pack size 40 μF 8173231 Run capacitor μF HHP015 Multipack 10 60 μF 120Z0050 Run capacitor μF HHP019 HHP021 Multipack 10 70 μF 120Z0051 Run capacitor μF HHP026 Multipack 10 50 μF 8173233 Run capacitor μF HHP030 Multipack 10 55 μF 8173234 Run capacitor μF HHP038 Multipack ...

Page 29: ...PVE 0 95 liter can HHP015 to 045 Multipack 1 Type Code No Description Application Packaging Pack Size 120Z5005 Mounting kit for 1 scroll compressor including 4 grommets 4 sleeves 4 bolts 4 washers All models Single pack 1 Type Code No Description Application Packaging Pack Size 7750009 Discharge thermostat kit All models Multipack 10 7973008 Discharge thermostat kit All models Industry pack 50 ...

Page 30: ......

Page 31: ......

Page 32: ...m We are offering a single source for one of the widest ranges of innovative refrigeration and air conditioning components and systems in the world And we back technical solutions with business solution to help your company reduce costs streamline processes and achieve your business goals Danfoss A S www danfoss com Danfoss can accept no responsibility for possible errors in catalogues brochures an...