7.3 Quick Menu
The Quick Menu gives easy access to the most frequently
used parameters.
1.
To enter the Quick Menu, press [Menu] key until
indicator in display is placed above
Quick Menu
.
2.
Use [
▲
] [
▼
] to select either QM1 or QM2, then
press [OK].
3.
Use [
▲
] [
▼
] to browse through the parameters in
the Quick Menu.
4.
Press [OK] to select a parameter.
5.
Use [
▲
] [
▼
] to change the value of a parameter
setting.
6.
Press [OK] to accept the change.
7.
To exit, press either [Back] twice to enter
Status
,
or press [Menu] once to enter
Main Menu
.
Illustration 7.9 Indicating Quick Menu Mode
7.4 Quick Menu Parameters
7.4.1 Quick Menu Parameters - Basic
Settings QM1
Below are descriptions of all parameters found in the Quick
Menu.
*
= Factory setting.
1-20 Motor Power [kW]/[HP] (P
m.n
)
Option:
Function:
Enter motor power from nameplate
data.
Two sizes down, one size up from
nominal VLT rating.
[1]
0.09 kW/0.12 HP
[2]
0.12 kW/0.16 HP
[3]
0.18kW/0.25 HP
[4]
0.25 kW/0.33 HP
[5]
0.37kW/0.50 HP
[6]
0.55 kW/0.75 HP
[7]
0.75 kW/1.00 HP
[8]
1.10 kW/1.50 HP
[9]
1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.0 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
NOTE
Changing this parameter affects parameter 1-22 to 1-25,
1-30, 1-33 and 1-35.
1-22 Motor Voltage (U
m.n
)
Range:
Function:
230/400 V [50 - 999 V] Enter motor voltage from nameplate
data.
1-23 Motor Frequency (f
m.n
)
Range:
Function:
50 Hz
*
[20-400 Hz] Enter motor frequency from nameplate
data.
Programming
VLT Micro Drive Design Guide
MG02K102 - VLT
®
is a registered Danfoss trademark
65