background image

”unit” in the scope this directive. Under all circum-

stances local safety regulations must be fulfilled.

 •  The unit must be securely installed on a stable 

and rigid support, and fixed from the begin-

ning. See picture 2.

 •  It is recommended to install the unit on rub-

ber grommets or vibration dampers . Rubber 

pads with mounting bolts are supplied.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as possible 

to avoid oil contamination from ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 

insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 31 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  

Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply 

to the compressor and provides 230V a.c. alarm 

signals (max.50VA) in case of activation. Version 

W04 is also equipped with phase sequence relay 

to protect the unit against phase loss/sequence/ 

asymmetry and under-/over-voltage.

For units with a 3-phase scroll compressor, cor-

rect phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main swit-

ch terminals T1, T2 and T3 respectively.

 DGT protection is required if the high and 

low pressure switch settings do not protect the 

compressor against operations beyond its spe-

cific application envelope. Please refer to the 

examples below, which illustrate where DGT 

protection is required (n°1) and where it is not 

(n°2). 

The compressor must not be allowed to cycle 

on the discharge gas thermostat. Continuous 

operations beyond the compressor’s operating 

range will cause serious damage to the com-

pressor!

Discharge line

Thermostat

Bracket

Insulation

A DGT accessory is available from Danfoss: refer 

to section “Spare parts & accessories”.

8 – Filling the system

 •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A / 

R507, R22, R452A or R448A/R449A and approx. 

2 bar for R134a and R513A.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices in compliance with both 

generally and locally applicable regulations and 

safety standards. 

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shut-down 

period.

10 – Start-up

 •  Never start the unit when no refrigerant is char-

ged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 •  Check that the protection sheet has been re-

moved from the backside of condenser.

 •  Balance the High Pressure / Low Pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

 •  Eventual reverse rotation of  a 3-phase com-

pressor can be detected by following phe-

nomena; unit doesn’t start, the compressor 

doesn’t build up pressure, it has abnormally 

high sound level and abnormally low power 

consumption. In such case, shut down the unit 

immediately and connect the phases to their 

proper terminals.

 •  If the rotation direction is correct the low pres-

sure indication on the low pressure gauge shall 

show a declining pressure and the high pres-

sure indication on the high pressure gauge 

shall show an increasing pressure.

11 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow com-

pressed air through the coil from the inside out, 

and brush with a soft bristle. Do not use a wire 

brush. Do not impact or scrape the coil with the 

vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to be 

done, it shall be done in such a way that no refri-

gerant can escape to the environment.

Instructions

2 | AN238286441930en-001101

© Danfoss | DCS (CC) | 2019.01

Summary of Contents for Optyma Slim Pac OP-MPZE060

Page 1: ...roller W10 only Refer version control for components details in all versions 2 Handling and storage It is recommended not to open the packaging before the unit is at the final place for installation Handle the unit with care The packaging al lows for the use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between 35...

Page 2: ... the filling cylinder connected to the circuit 9 Verification before commissioning Use safety devices in compliance with both generally and locally applicable regulations and safety standards Verify that all electrical connections are properly fastenedandincompliancewithlocalregulations When a crankcase heater is required it must be energized at least 12 hours before initial start up and start up ...

Page 3: ... X X Filter drier X X X X Sight Glass X X X X Solenoid Valve X Cranckase Heater X X Full Ebox X X X Fan speed controller X Dual Pressure switch KP X X X X Only for LBP Model 13 Warranty Always transmit the model number and serial num ber with any claim filed regarding this product The product warranty may be void in following cases Absence of nameplate External modifications in particular drilling...

Page 4: ... LP HP signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP man reset LP aut reset Manual test Convertible reset Manual reset LP auto HP man LP auto HP auto LP diff Manual reset Test Test Resist Load Pilot duty AC DC Max 50 VA Instructions 4 AN2382864419...

Page 5: ...OP LPQE067 084 098 OP MPVE068 080 093 099 108 OP LPQE048 068 OP MPVE034 046 057 OP MPME048 060 B2 B3 Instructions AN238286441930en 001101 5 Danfoss DCS CC 2019 01 ...

Page 6: ...46MLW02G OP MPVE048MTW02G OP MPVE060MTW02G OP MPZE060MTW02G Code G version W02 OP MPVE034 046 OP MPME048 060 OP MPZE060 Code G version W02 OP MPVE068 080 093 WD1 WD2 Instructions 6 AN238286441930en 001101 Danfoss DCS CC 2019 01 ...

Page 7: ...060MLW02E Code E version W02 OP MPVE034 046 068 080 099 108 OP MPME048 060 OP MPVE034MLW04G OP MPVE046MLW04G OP MPVE048MLW04G OP MPVE057MLW04G OP MPVE060MLW04G OP LPQE048NTW04G OP LPQE068NTW04G Code G version W04 OP MPVE034 046 057 OP MPME048 060 LPQE048 068 WD3 WD4 Instructions AN238286441930en 001101 7 Danfoss DCS CC 2019 01 ...

Page 8: ...ME060MTW04E OP LPQE048NTW04E OP LPQE068NTW04E OP LPQE067LLW04E OP LPQE084LLW04E OP LPQE098LLW04E Code E version W04 OP MPVE034 046 057 068 080 099 108 OP MPME048 060 OP LPQE048 067 068 084 098 MPVE068MLW04G MPVE080MLW04G MPVE093MLW04G Code G version W04 OP MPVE068 080 093 WD5 WD6 Instructions 8 AN238286441930en 001101 Danfoss DCS CC 2019 01 ...

Page 9: ...MPVE080MLW08E OP MPVE099MLW08E OP MPVE034MLW10G OP MPVE057MLW10G OP LPQE048NTW10G OP LPQE068NTW10G OP MPVE046MLW10G OP MPVE068MLW10G OP MPVE080MLW10G Code G version W10 OP MPVE034 046 057 068 080 OP LPQE048 068 WD7 WD8 Instructions AN238286441930en 001101 9 Danfoss DCS CC 2019 01 ...

Page 10: ...it H1 Low pressure alarms H2 High pressure alarms M1 Compressor M2 Fan motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Legend BK black BU blue BN brown GY grey RD red WH white OP MPVE046MLW10E OP MPVE057MLW10E OP MPVE068MLW10E OP MPVE080MLW10E OP MPVE099...

Page 11: ...Instructions AN238286441930en 001101 11 Danfoss DCS CC 2019 01 ...

Page 12: ...s the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...

Reviews: