 Installation and servicing of the conden-

sing units by qualified personnel only. 

Follow these instructions and sound refri-

geration engineering practice relating to 

installation, commissioning, maintenance 

and service.

 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

 Under all circumstances, the EN378 (or  

other applicable local safety regulation) 

requirements must be fulfilled.

The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation» 

section for further details. 
The condensing unit must be handled with cau-

tion in the vertical position (maximum offset 

from the vertical : 15°)

MADE IN INDIA

OP-MPVE034MLW04E

Application

Refrigerant

M.W.P. HP

114X7039

MBP

(1) R404A, R507, R22, 

     R448A, R449A, R452A

(1) 28 bar

             LP (1)  7  bar

IP54

(2) R134a, R513A

(2) 23 bar

(2)  5  bar

Voltage

380-400V3N~/50Hz

LRA

OIL INSIDE   POE 46

30.5 A

7.5 A

MCC

Serial No.

EAN No.

Danfoss A/S, 6430 Nordborg, Denmark

Barcode Serial No: 

123456CG0514

XXXXXXXXXXX

118UXXXX

A
B
C

D
E
F

G

A:   Model

B:   Code  number 

C:   Application,  Protection

D:   Refrigerant 

E:   Housing Service Pressure

F:   Supply voltage, Locked Rotor Ampere,  

Maximum Current Consumption

G:   Serial Number and bar code

Name plate

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Picture 2 

Mounting bolts 

1 – Introduction

These instructions pertain to Optyma

TM

 Slim 

Pack condensing units OP-LPQE/MPVE/MPME 

(R22, R404A, R507, R134a, R513A, R448A, R449A, 

R452A) used for refrigeration systems. They pro-

vide necessary information regarding safety and 

proper usage of this product.

The condensing unit includes following:

  •  Scroll/reciprocating  compressor

 •  Microchannel heat exchanger

 •  Dual pressure switches

 •  Service valves suction/ liquid

 •  Weather proof housing (IP 54)

  •  Filter  drier

 •  Receiver with stop valve

  •  Sight  glass

  •  Solenoid  valve

 •  Phase sequence relay *

)

 •  Fully pre-wired electrical panel (including main 

switch, compressors contactor, overload relay)

 •  Crankcase heater (OP-LPQE units in W04 and 

W10 only)*

)

Fan speed controller (W10 only)

*

)

 Refer version control for components details in 

all versions

2 – Handling and storage

 •  It is recommended not to open the packaging 

before the unit is at the final place for installation.

 •  Handle the unit with care. The packaging al-

lows for the use of a forklift or pallet jack. Use 

appropriate and safe lifting equipment. 

 •  Store and transport the unit in an upright position.

 •  Store the unit between -35°C and 50°C.

 •  Don’t expose the packaging to rain or corrosive 

atmosphere.

 •  After unpacking, check that the unit is com-

plete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 

 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.

 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture1 

for minimal values of distance to walls.

 •  Avoid installing the unit in locations which are daily 

exposed to direct sunshine for longer periods.

 •  Avoid installing the unit in aggressive and dus-

ty environments.

 •  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable enough 

to carry the entire unit weight and to eliminate 

vibrations and interference.

 •  The unit ambient temperature may not exceed 

50°C during off-cycle.

 •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

 •  When installing units for HFC refrigerants, use 

equipment specifically reserved for HFC refri-

gerants which was never used for CFC or HCFC 

refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 •  The suction piping connected to the compres-

sor must be flexible in 3 dimensions to dampen 

vibrations. Furthermore piping has to be done 

in such a way that oil return for the compres-

sor is ensured and the risk of liquid slug over in 

compressor is eliminated.

4 – Installation

 •  The installation in which the condensing unit is ins-

talled must comply to EEC Pressure directive (PED) 

no. 2014/68/EU. The condensing unit itself is not a 

Picture 3 

Anticlockwise (open)

Clockwise (Close)

Schrader valve

Instructions

Optyma™

 

Slim Pack 

OP-LPQE/MPVE/MPME

© Danfoss | DCS (CC)| 2019.01

AN238286441930en-001101 | 1 

Summary of Contents for Optyma Slim Pac OP-MPZE060

Page 1: ...roller W10 only Refer version control for components details in all versions 2 Handling and storage It is recommended not to open the packaging before the unit is at the final place for installation Handle the unit with care The packaging al lows for the use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between 35...

Page 2: ... the filling cylinder connected to the circuit 9 Verification before commissioning Use safety devices in compliance with both generally and locally applicable regulations and safety standards Verify that all electrical connections are properly fastenedandincompliancewithlocalregulations When a crankcase heater is required it must be energized at least 12 hours before initial start up and start up ...

Page 3: ... X X Filter drier X X X X Sight Glass X X X X Solenoid Valve X Cranckase Heater X X Full Ebox X X X Fan speed controller X Dual Pressure switch KP X X X X Only for LBP Model 13 Warranty Always transmit the model number and serial num ber with any claim filed regarding this product The product warranty may be void in following cases Absence of nameplate External modifications in particular drilling...

Page 4: ... LP HP signal Contacts Cut In Cut In Cut In Cut out Cut out Cut out Differential Differential fixed Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP man reset LP aut reset Manual test Convertible reset Manual reset LP auto HP man LP auto HP auto LP diff Manual reset Test Test Resist Load Pilot duty AC DC Max 50 VA Instructions 4 AN2382864419...

Page 5: ...OP LPQE067 084 098 OP MPVE068 080 093 099 108 OP LPQE048 068 OP MPVE034 046 057 OP MPME048 060 B2 B3 Instructions AN238286441930en 001101 5 Danfoss DCS CC 2019 01 ...

Page 6: ...46MLW02G OP MPVE048MTW02G OP MPVE060MTW02G OP MPZE060MTW02G Code G version W02 OP MPVE034 046 OP MPME048 060 OP MPZE060 Code G version W02 OP MPVE068 080 093 WD1 WD2 Instructions 6 AN238286441930en 001101 Danfoss DCS CC 2019 01 ...

Page 7: ...060MLW02E Code E version W02 OP MPVE034 046 068 080 099 108 OP MPME048 060 OP MPVE034MLW04G OP MPVE046MLW04G OP MPVE048MLW04G OP MPVE057MLW04G OP MPVE060MLW04G OP LPQE048NTW04G OP LPQE068NTW04G Code G version W04 OP MPVE034 046 057 OP MPME048 060 LPQE048 068 WD3 WD4 Instructions AN238286441930en 001101 7 Danfoss DCS CC 2019 01 ...

Page 8: ...ME060MTW04E OP LPQE048NTW04E OP LPQE068NTW04E OP LPQE067LLW04E OP LPQE084LLW04E OP LPQE098LLW04E Code E version W04 OP MPVE034 046 057 068 080 099 108 OP MPME048 060 OP LPQE048 067 068 084 098 MPVE068MLW04G MPVE080MLW04G MPVE093MLW04G Code G version W04 OP MPVE068 080 093 WD5 WD6 Instructions 8 AN238286441930en 001101 Danfoss DCS CC 2019 01 ...

Page 9: ...MPVE080MLW08E OP MPVE099MLW08E OP MPVE034MLW10G OP MPVE057MLW10G OP LPQE048NTW10G OP LPQE068NTW10G OP MPVE046MLW10G OP MPVE068MLW10G OP MPVE080MLW10G Code G version W10 OP MPVE034 046 057 068 080 OP LPQE048 068 WD7 WD8 Instructions AN238286441930en 001101 9 Danfoss DCS CC 2019 01 ...

Page 10: ...it H1 Low pressure alarms H2 High pressure alarms M1 Compressor M2 Fan motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Legend BK black BU blue BN brown GY grey RD red WH white OP MPVE046MLW10E OP MPVE057MLW10E OP MPVE068MLW10E OP MPVE080MLW10E OP MPVE099...

Page 11: ...Instructions AN238286441930en 001101 11 Danfoss DCS CC 2019 01 ...

Page 12: ...s the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...

Reviews: