background image

4 – Installation

 •  The installation in which the condensing unit is ins-

talled must comply to EU Pressure directive (PED) 

no. 2014/68/EU. The condensing unit itself is not a 

”unit” in the scope this directive. Under all circum-

stances local safety regulations must be fulfilled.

 •  The unit must be securely installed on a stable 

and rigid support, and fixed from the begin-

ning. See picture 2.

 •  It is recommended to install the unit on rub-

ber grommets or vibration dampers . Rubber 

pads with mounting bolts are supplied.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as possible 

to avoid oil contamination from ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 •  Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

 •  Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

 •  CU function and reliability is ensured/verified 

for super heat 10K (SH 10K) condition so, it is 

recommended to insulate the suction pipe up 

to the compressor inlet with 19 mm thick insu-

lation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 32 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 •  Refer to wiring diagram for electrical connec-

tions details.

 •  Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local stan-

dards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply to 

the compressor in case of activation. 

8 – Filling the system

 •  Wear protective stuff like goggles and protec-

tive gloves.

 •  Never start the compressor under vacuum. 

Keep the compressor switched off.

 •  Before charging the refrigerant, verify that the 

oil level is between ¼ and ¾ on the compressor 

oil sight glass. If additional oil is required please 

refer to the compressors label for type of oil.

 •  Use only the refrigerant for which the unit is 

designed for.

 •  Fill the refrigerant in liquid phase into the 

condenser or liquid receiver. Ensure a slow 

charging of the system to 4 – 5 bar for R404A.

 •  Do not put liquid refrigerant through suction line.

 •  It is not allowed to mix additives with the oil 

and/or refrigerant

 •  The remaining charge is done until the instal-

lation has reached a level of stable nominal 

condition during operation.

 •  Never leave the filling cylinder connected to 

the circuit.

9 – Verification before commissioning

 Use safety devices in compliance with both 

generally and locally applicable regulations and 

safety standards. 

 •  Verify that all electrical connections are properly 

fastened and in compliance with local regulations.

 •  When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-

up and start-up after prolonged shut-down 

period.

10 – Start-up

 •  Never start the unit when no refrigerant is char-

ged.

 •  All service valves must be in the open position.

See picture 3.

 •  Check compliance between unit and power 

supply.

 •  Check that the crankcase heater is working.

 •  Check that the fan can rotate freely.

 •  Balance the High Pressure / Low Pressure.

 •  Energize the unit. It must start promptly. If 

the compressor does not start, check wiring 

conformity, voltage on terminals and sequence 

phase.

11 – Check with running unit

 •  Check the fan rotation direction. Air must flow 

from the condenser towards the fan.

 •  Check current draw and voltage.

 •  Check suction superheat to reduce risk of slug-

ging.

 •  When a sight glass is provided observe the oil 

level at start and during operation to confirm 

that the oil level remains visible.

 •  Respect the operating limits.

 •  Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side as 

far away as possible from the compressor. The 

compressor must be operating during this pro-

cess.

 •  Do not overcharge the system.

 •  Never release refrigerant to atmosphere.

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 

cleanliness, noise and leak detection.

 •  Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

 Always switch off the unit at main switch 

before remove fan panel.

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.

Maintenance operators and installers require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 

regulations are performed.

 This appliance is not intended for use by per-

sons (including children) with reduced physical, 

sensory or mental capabilities, or lack of expe-

rience and knowledge, unless they have been gi-

ven supervision or instruction concerning use of 

the appliance by a person responsible for their 

safety. Children should be supervised to ensure 

that they do not play with the appliance

To prevent system related problems, following

Periodic  maintenance is recommended:

 •  Verify that safety devices are operational and 

properly set.

 •  Ensure that the system is leak tight.

 •  Check the compressor current draw.

 •  Confirm that the system is operating in a way 

consistent with previous maintenance records 

and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 •  Keep the unit clean and verify the absence of 

rust and oxidation on the unit components, 

tubes and electrical connections.

The condenser must be checked at least once 

a year for clogging and be cleaned if deemed 

necessary. Access to the internal side of the 

condenser takes place through the fan panel. 

Microchannel coils tend to accumulate dirt on 

the surface rather than inside, which makes 

them easier to clean than fin-&-tube coils.

 •  Switch off the unit at main switch before re-

move any panel from the condensing unit.

 •  Remove surface dirt, leaves, fibres, etc. with 

a vacuum cleaner, equipped with a brush or 

other soft attachment. Alternatively, blow com-

pressed air through the coil from the inside out, 

and brush with a soft bristle. Do not use a wire 

brush. Do not impact or scrape the coil with the 

vacuum tube or air nozzle.

If the refrigerant system has been opened, the 

system has to be flushed with dry air or nitrogen 

to remove moisture and a new filter drier has to

be installed. If evacuation of refrigerant has to be 

done, it shall be done in such a way that no refri-

gerant can escape to the environment.

13 - Warranty

Always transmit the model number and serial num-

ber with any claim filed regarding this product.

The product warranty may be void in following 

cases:

 •  Absence of nameplate.

 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

 •  Compressor opened or returned unsealed.

 •  Rust, water or leak detection dye inside the 

compressor.

 •  Use of a refrigerant or lubricant not approved 

by Danfoss.

 •  Any deviation from recommended instructions 

pertaining to installation, application or main-

tenance.

 •  Use in mobile applications.

 •  Use in explosive atmospheric environment.

 •  No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that condensing 

units and oil should be recycled by a 

suitable company at its site.

Instructions

2 |  © Danfoss | DCS (CC) | 2017.12

FRCC.PI.056.A2.02

Summary of Contents for Optyma OP-LPHE Series

Page 1: ...use of a forklift or pallet jack Use appropriate and safe lifting equipment Storeandtransporttheunitinanuprightposition Store the unit between 35 C and 60 C Don t expose the packaging to rain or corrosive atmosphere After unpacking check that the unit is com plete and undamaged 3 Installation precautions Do not braze as long the condensing unit is under pressure Neverplacetheunitinaflammableatmosp...

Page 2: ...essure Low Pressure Energize the unit It must start promptly If the compressor does not start check wiring conformity voltage on terminals and sequence phase 11 Check with running unit Check the fan rotation direction Air must flow from the condenser towards the fan Check current draw and voltage Check suction superheat to reduce risk of slug ging When a sight glass is provided observe the oil lev...

Page 3: ...PZE086MTW07V OP MPZE086MTW07N OP MPZE086MTW07Q H3 H3 H3 380V 3N 60Hz 230V 1N 60Hz 230V 3 60Hz OP MPZE060 068 086 OP LPHE108 136 2SW PD LJK PELHQW 3DFN 114X7140 LBP LBP LBP LBP LBP LBP MBP MBP MBP MBP MBP APP UNIT DESCRIPTION CHASSIS POWER SUPPLY COMP 114X7150 114X7153 114X7120 114X7141 114X7151 114X7146 114X7156 114X7117 114X7123 114X7157 NTZ048 NTZ048 NTZ048 NTZ068 NTZ068 NTZ068 MTZ018 MTZ018 MTZ...

Page 4: ... MTZ072 MTZ100 MTZ100 OP LPHE215NTW07Q OP LPHE215NTW07V OP LPHE271NTW07V OP LPHE271NTW07Q OP MPZE108MTW07N OP MPZE108MTW07V OP MPZE108MTW07Q OP MPZE0121MTW07V OP MPZE121MTW07Q OP MPZE171MTW07V OP MPZE171MTW07Q H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 H4 230V 3 60Hz 380V 3N 60Hz 380V 3N 60Hz 230V 3 60Hz 230V 1N 60Hz 380V 3N 60Hz 230V 3 60Hz 380V 3N 60Hz 230V 3 60Hz 380V 3N 60Hz 230V 3 60Hz OP MPZE108 121 171 ...

Page 5: ...o LP auto LP man HP man HP man HP auto HP auto P H t e s e r n a m P L t e s e r t u a P L AC1 16 A DC 11 LR 112A AC3 16 A 400 V 12 W AC1110 A 220 V When used acc to UL regulations 1 bar Pe 30in Hg Convertible reset KP 15 15A 17W 17B KP 17B 060 539366 060 539466 LP auto LP auto HP man HP auto Instructions Danfoss DCS CC 2017 12 5 FRCC PI 056 A2 02 ...

Page 6: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions 6 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 ...

Page 7: ...tor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions Danfoss DCS CC 2017 12 7 FRCC PI 056 A2 02 ...

Page 8: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions 8 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 ...

Page 9: ...C2 Run Capacitor Compressor C3 C4 Run capacitor Fan E1 Crankcase Heater F1 Main Switch F2 Overload Relay F3 F4 Fuse Control Circuit F5 Discharge Thermostat LBP only M1 Compressor M2 M3 Fan Motor K1 Compressor contactor K2 Start Relay R1 R2 Bleeder Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white Instructions Danfoss DCS CC 2017 12 9 FRCC PI 056 A2 02 ...

Page 10: ...der Resistor S1 Door Limit Switch Legend BK black BU blue BN brown GY grey RD red WH white 10 Danfoss DCS CC 2017 12 FRCC PI 056 A2 02 Danfoss can accept no responsibility for possible errors in catalogues brochures and other printed material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made wit...

Reviews: